SNT120CPK EATON CUTLER HAMMER, SNT120CPK Datasheet - Page 193

Shunt Trip

SNT120CPK

Manufacturer Part Number
SNT120CPK
Description
Shunt Trip
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of SNT120CPK

Operating Voltage
120VAC
For Use With
EG And JG Frame Series G Circuit Breakers
November 2008
N-Frame
Table 12-315. 600 Vac Maximum
Note: All HMCP 800 A and 1200 A come without terminals. For Terminals, see Table 12-307
on Page 12-187.
CA08101001E
NEMA
Starter
Size
7
7
7
7
7
7
7
8
8
8
8
8
8
8
Equipped with electronic trip device.
Motor FLA ranges are typical. The corresponding trip setting is at 13X the minimum FLA value
shown. Where a 13X setting is required for an intermediate FLA value, alternate cam settings and/
or MCP ratings should be used.
Cont.
Amps
1200
800
Cam
Setting
A
B
C
D
E
F
G
A
B
C
D
E
F
G
Motor Full
Load Current
Amperes (FLA)
123.1 – 184.5
184.6 – 246.1
246.2 – 307.6
307.7 – 369.1
369.2 – 430.7
430.8 – 492.2
492.3 – 553.7
184.6 – 276.8
276.9 – 369.1
369.2 – 461.4
461.5 – 553.7
553.8 – 646.1
646.2 – 738.4
738.5 – 830.7
For more information visit: www.eaton.com
Series C Molded Case Circuit Breakers
Motor Circuit Protectors
N-Frame
MCP
Trip
Setting
1600
2400
3200
4000
4800
5600
6400
2400
3600
4800
6000
7200
8400
9600
MCP
Catalog
Number
HMCP800X7W
HMCP12Y8W
Price
U.S. $
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . CB-2
12-193