RELAY CARD-INT SOLA HEVI DUTY, RELAY CARD-INT Datasheet - Page 33

no-image

RELAY CARD-INT

Manufacturer Part Number
RELAY CARD-INT
Description
Intellislot Relay Card
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of RELAY CARD-INT

Features
Provides Dry Contact Relay Outputs For Custom Wired Applications And Delivers Support For Built-in Shutdown For AS/400 Systems
Accessory Type
Relay Card
For Use With
S4K5U
Lead Free Status / RoHS Status
na
1. Remove the 5U bezel panel on the front of the UPS
2. Remove battery access door by loosening the
3. Use a Phillips (cross-head) screwdriver to remove
4. Disconnect the battery connectors in the front of
5. Lift the internal connector out of the way and slide
6. Unpack the new battery assembly, taking care not
7. Line up and slide in the new replacement battery
8. Reconnect the electrical connections for each
9. Install the battery retaining brackets using the
10. Install the battery access panel and tighten the
by removing the screws located on the sides of the
bezel (see illustration at right).
captive screws and tipping the panel forward. Lift
to remove it from the main cabinet.
the screw in the battery retaining bracket on each
battery pack (see illustration at right). Remove the
retaining brackets.
each battery pack.
the battery out of the UPS. Support the weight of
the battery to prevent it from falling.
to destroy the packing. Compare new and old
battery assemblies to make sure they are the
same. If so, proceed with Step 7; otherwise STOP
and contact your local dealer, Sola/Hevi-Duty
representative or the Sola/Hevi-Duty Technical
Support Services.
pack while holding the internal connector out of
the way.
battery pack.
Phillips removed earlier.
captive screws.
NOTE
These are hot-swappable replacement
batteries. However, caution should be
exercised because during this procedure the
load is unprotected from disturbances and
power outages.
27
Retaining screw
5U Bezel with Battery Access
Battery Access Bezel Screws
Door Behind Bezel
Battery Connectors
UPStation GXT
- +
AC INPUT
BATTERY UPS ON
BYPASS
Retaining bracket
UPStation GXT
- +
AC INPUT
BATTERY UPS ON
BYPASS