RELAY CARD-INT SOLA HEVI DUTY, RELAY CARD-INT Datasheet - Page 23

no-image

RELAY CARD-INT

Manufacturer Part Number
RELAY CARD-INT
Description
Intellislot Relay Card
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of RELAY CARD-INT

Features
Provides Dry Contact Relay Outputs For Custom Wired Applications And Delivers Support For Built-in Shutdown For AS/400 Systems
Accessory Type
Relay Card
For Use With
S4K5U
Lead Free Status / RoHS Status
na
6.0
I
1. Verify that the Input Output circuit breakers are off.
2. During initial system checks, disconnect all loads (open load disconnects).
3. Inspect all wiring, cables, and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted
5. If you are using a distribution box that includes a Manual Bypass Switch, place the switch in
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.
7. Using a voltmeter, verify the expected L1-N voltage.
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power,
9. Close the Input circuit breaker located on the distribution box. The green AC INPUT lamp should
10. Press the ON button for 1 second. The BYPASS lamp will light for several seconds before the UPS
11. Close the Output circuit breaker on the rear of the UPS. If a Manual Bypass Switch is used, the
12. Perform a Manual Battery Test - Press the ON button for 1 second. The front BATTERY lamp will
13. Review all setting option provided by the configuration program. Some changes require that the
14. Connect all loads for normal operation.
NITIAL
in the sockets.
BYPASS position.
If no Manual Bypass Switch is used, there will be no output voltage at this time. If a Manual
Bypass Switch is used, verify that the same voltages appear at the Output terminals. If a Manual
Bypass Switch is used, the Bypass lamp will light by the switch. If no manual bypass switch is
used, there will be no output voltage at this time.
close all access panels to the distribution box, and reapply input power.
illuminate on the front panel.
ON lamp turn on continuously. If the batteries are determined to charged above 80%, an
automatic battery test will run for about 15 seconds.
Inverter lamp by the switch will light. If a Manual Bypass Switch is used, transfer the switch to
the Inverter position. The output terminal block will be powered at this time.
light for about 15 seconds and then return to only the UPS ON and AC INPUT lamps being on.
UPS be OFF. If this is the case, these should be programmed before powering the loads. The
configuration program is described in the next section.
S
TART
-U
P AND
E
LECTRICAL
17
C
HECKS
Initial Start-Up and Electrical Checks