SNAP-AIPM OPTO 22, SNAP-AIPM Datasheet - Page 8

Power Monitoring Module

SNAP-AIPM

Manufacturer Part Number
SNAP-AIPM
Description
Power Monitoring Module
Manufacturer
OPTO 22
Type
Inputr
Datasheets

Specifications of SNAP-AIPM

Accessory Type
Single-phase Power Monitoring Module
Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Signal Input Type
85 To 250V And 0 To 10A RMS
Brand/series
SNAP Series
Connection To Host
Backplane
Current, Input
100 mA
Current, Supply
0 to 10 A
Dimensions
82.55mmL×18.29mmW×90.17mmH
Input
85 to 250/0 to 10 VAC/AAC
Input Resolution
10 mV
Input Type
Analog
Input, Range
85 to 250/0 to 10 VAC/AAC
Mounting Type
PCB
Number Of Channels
2
Number Of Inputs
2 Channels
Primary Type
Control
Resistance, Input
1 Megohms
Special Features
Transformer Isolation, Optical Isolation
Standards
UL, CSA, CE Certified
Temperature, Operating
0 to +70 °C
Voltage, Isolation
4000 V
Voltage, Supply
5 VDC
No. Of Analog Inputs
4
Resolution
10mV, 400uA
Rohs Compliant
No
For Use With
Snap I/O Modules
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
PAGE
8
Scaling Example 3: SNAP-AIPM-3 without PT
Leave Actual values at their defaults for all points, and leave
Lower Scaled values at 0. Calculate Upper Scaled values for
points as follows:
Points 0, 4, 8: Always 300 volts
and 300 VAC. (For line voltage over 300 V, use Example 2.)
Points 1, 5, 9: 5* (CT primary / CT secondary)
Points 2, 6, 10: Upper Scaled for voltage * Upper Scaled for
current (ex. Upper Scaled for pt 0 * Upper Scaled for pt 1)
Points 3, 7, 11: Upper Scaled for voltage * Upper Scaled for
current
Points 12, 13: 3 * Upper Scaled for voltage * Upper Scaled
for current
Example
Voltage: 240 VAC (no potential transformer required)
Current: 180 amps (requires CT primary of 200).
CT has a secondary of 5 A.
So to calculate points 1, 5, 9: 5 * (200/5) = 200
...points 2, 6, 10, 3, 7, 11: 300 * 200 = 60,000
...points 12, 13: 3 * 300 * 200 = 180,000
1 IMPORTANT—Voltage change: Older SNAP-AIPM-3
modules used 0–250 volts and 0–10 amps. Before wiring or
scaling, check the printed information on the module to make
sure you are using the correct voltage and current. Contact
Product Support to exchange older modules.
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Units
Lower
Upper
Units
Lower
Upper
Units
Lower
Upper
VAC/VDC VAC/VDC
True Power & ABS
Actual
Actual
Actual
1500
4500
300
Points 2, 6, 10
Points 12 & 13
W
Points 0, 4, 8
0
0
0
J
Voltage
Watts
180,000
Scaled
Scaled
60,000
Scaled
300
W
0
0
J
0
1
for line voltage between 85
Actual
Actual
1500
Points 3, 7, 11
VA
Points 1, 5, 9
A
0
5
0
Volt Amps
Current
Scaled
Scaled
60,000
200
VA
A
0
0
SNAP Power Monitoring Modules
Scaling Example 4: SNAP-AIPM-3 with PT
For line voltage higher than 300 VAC
potential transformer (PT) must be used.
Leave Actual values at their defaults for all points, and leave
Lower Scaled at 0. Calculate Upper Scaled values for points as
follows:
Points 0, 4, 8: 300 * PT ratio
Points 1, 5, 9: 5* (CT primary / CT secondary)
Points 2, 6, 10: Upper Scaled for voltage * Upper Scaled for
current (ex. Upper Scaled for pt 0 * Upper Scaled for pt 1)
Points 3, 7, 11: Upper Scaled for voltage * Upper Scaled for
current
Points 12, 13: 3 * Upper Scaled for voltage * Upper Scaled
for current
Example
Voltage: 480 VAC (requires potential transformer).
PT ratio is 2:1
Current: 350 amps (Requires CT primary of 400. CT has a
secondary of 5 A.
So to calculate points 0, 4, 8: 300 * 2 = 600
...points 1, 5, 9: 5 * (400/5) = 400
...points 2, 6, 10, 3, 7, 11: 600 * 400 = 240,000
...points 12, 13: 3 * 600 * 400 = 720,000
Units
Lower
Upper
Units
Lower
Upper
Units
Lower
Upper
VAC/VDC VAC/VDC
True Power & ABS
Actual
Actual
Actual
1500
4500
300
Points 2, 6, 10
Points 12 & 13
W
Points 0, 4, 8
0
0
0
J
Voltage
Watts
240,000
720,000
Scaled
Scaled
Scaled
600
W
0
0
J
0
Actual
Actual
1500
VA
Points 3, 7, 11
1
Points 1, 5, 9
A
0
5
0
, a step-down
Volt Amps
Current
240,000
Scaled
Scaled
400
VA
A
0
0

Related parts for SNAP-AIPM