E5CSVR1TD500ACDC24V Omron, E5CSVR1TD500ACDC24V Datasheet - Page 3

TEMPERATURE CONTROLLER, RELAY OP

E5CSVR1TD500ACDC24V

Manufacturer Part Number
E5CSVR1TD500ACDC24V
Description
TEMPERATURE CONTROLLER, RELAY OP
Manufacturer
Omron
Datasheet

Specifications of E5CSVR1TD500ACDC24V

Thermocouple Type
T
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Output Voltage Max
250VAC
Svhc
No SVHC (15-Dec-2010)
Accuracy
± 0.5%
Approval Bodies
CE, CRUus
Colour
Black
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Note: 1. The following exceptions apply to thermocouples.
Setting accuracy
Indication accuracy
(ambient temperature of 23 ° C)
Influence of temperature
Influence of voltage
Hysteresis (for ON/OFF control)
Proportional band (P)
Integral time (I)
Derivative time (D)
Alarm output range
Control period
Sampling period
Insulation resistance
Dielectric strength
Vibration
resistance
Shock resistance
Life expectancy
Weight
Degree of protection
Memory protection
EMC
Approved standards
Conformed standards
Characteristics
Electrical Life Expectancy Curve for Relays (Reference Values)
500
300
100
2. The following exceptions apply to platinum resistance thermometers.
50
30
10
5
3
1
0
• U, L: ±2 ° C ±1 digit max.
• R:
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Input set value 1 for E5CSV: 0.5% FS ±1 digit max.
E5CSV
250 VAC, 30 VDC
(resistive load)
cosφ = 1
1
±3 ° C ±1 digit max. at 200 ° C or less
Malfunction 10 to 55 Hz, 20 m/s
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s
Destruction 300 m/s
Electrical
2
3
Thermocouple (See note 1.):
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1 ° C, whichever is greater) ±1 digit max.
R thermocouple inputs:
Other thermocouple inputs:
Platinum resistance thermometer inputs: (±1% of PV or ±2 ° C, whichever is greater) ±1 digit max.
0.2% FS (0.1% FS for multi-input (thermocouple/platinum resistance thermometer) models)
1 to 999 ° C (automatic adjustment using auto-tuning/self-tuning)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Absolute-value alarm: Same as the control range
Other:
Alarm hysteresis:
2/20 s
500 ms
20 M Ω min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
100,000 operations min. (relay output models)
Approx. 120 g (Controller only)
Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMI Radiated:
EMI Conducted:
ESD Immunity:
Radiated Electromagnetic Field Immunity:
Conducted Disturbance Immunity:
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
UL 61010C-1 (listing)
CSA C22.2 No.1010-1
EN 61326, EN 61010-1, IEC 61010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
Switching current (A)
4
2
2
5
min., 3 times each in 6 directions
min., 3 times each in 6 directions
6
2
for 10 min each in X, Y, and Z directions
0% to 100% FS
0.2 ° C or ° F (fixed)
(±1% of PV or ±10 ° C, whichever is greater) ±1 digit max.
(±1% of PV or ±4 ° C, whichever is greater) ±1 digit max.
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61000-4-2: 4 kV contact discharge (level 2)
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
EN 61000-4-5: Power line:
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
(±0.5% of indication value or ±1 ° C, whichever is greater) ±1 digit max.
Temperature Controllers
8 kV air discharge (level 3)
10 V/m (900 MHz pulse modulated)
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Normal mode 1 kV; Common mode 2 kV
E5CSV