C500TS502 Omron, C500TS502 Datasheet - Page 37

no-image

C500TS502

Manufacturer Part Number
C500TS502
Description
RTD INPUT MODULE
Manufacturer
Omron
Datasheet

Specifications of C500TS502

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Module Memory Map
Read/
write
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Memory
map word
25
26
26
27
27
28
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
Bits
8 to 15
0 to 7
8 to 15
0 to 7
8 to 15
0 to 7
8 to 15
0 to 7
1 thru 8
1 thru 8
1 thru 8
1 thru 8
1 thru 8
1 thru 8
1 thru 8
1 thru 8
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Input
point
Function
Peak hold enable bits
BCD/binary select bits
Scaling enable bits
Averaging enable bits
Filtering enable bits
Low alarm enable bits
High alarm enable bits
°C/°F select bits
Low alarm limit
High alarm limit
Low alarm limit
High alarm limit
Low alarm limit
High alarm limit
Low alarm limit
High alarm limit
Low alarm limit
High alarm limit
Low alarm limit
High alarm limit
Low alarm limit
High alarm limit
Low alarm limit
High alarm limit
Description
These bits are set by the user to
enable/disable the peak hold function
for each input point. The default value
is disabled (0) for all input points.
These bits are set by the user to
select the data format used by each
input point. BCD = 1 and binary = 0.
This selection specifies the format of
the conversion data in words 01 to 08
and peak hold data in words 11 to 18.
BCD and binary can be used at the
same time for different input points.
NOTE: When specifying a data for-
mat for an input point, all module
memory map words for that specific
input point must have the same for-
mat. Mixing formats for an input point
will cause erroneous results to be re-
ported. The default value is BCD (1)
for all input points.
These bits are set by the user to
enable/disable the scaling function for
each input point. The default value is
disabled (0) for all input points.
These bits are set by the user to
enable/disable the Averaging function
for each input point. The default value
is disabled (0) for all input points.
These bits are set by the user to
enable/disable the filtering function
for each input point. The default value
is disabled (0) for all input points.
These bits are set by the user to
enable/disable the low alarm function
for each input point. The default value
is disabled (0) for all input points.
These bits are set by the user to
enable/disable the high alarm
function for each input point. The
default value is disabled (0) for all
input points.
These bits are set by the user to
select the scale format used by each
input point. Celsius = 0 and
Fahrenheit = 1. This selection
specifies the format of the conversion
data in words 01 to 08 and peak hold
data in words 11 to 18. °C and °F can
be used at the same time for different
input points. The default value is °C
(0) for all input points.
These words contain the low and
high alarm limits for each input point.
The format of these values should
match the data format selected for
each input point in word 26. Valid
values are -32767 to +32767 (8001 to
7FFF) binary and -7999 to +7999
BCD. Alarm limits must be specified
in scaled units if the scaling function
is enabled for the input point. The
default values are 0100 for the low
limit and 3900 for the high limit.
Section 5-1
31