C500TS502 Omron, C500TS502 Datasheet - Page 30

no-image

C500TS502

Manufacturer Part Number
C500TS502
Description
RTD INPUT MODULE
Manufacturer
Omron
Datasheet

Specifications of C500TS502

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Intelligent Functions
4- -3- -5
4- -3- -6
24
Peak Hold
Alarms
Note: When changing reporting modes from binary to BCD or from BCD to binary
The peak hold function can be used to detect peak conversion values of rap-
idly changing analog input signals. These values are stored in separate
memory locations in the module memory map. This data is reset each time
the peak hold function is enabled for the input point. The Peak Hold Reset
Bits and Acknowledge flags, which are available in the I/O Words, are de-
scribed in Section 5.
To apply the peak hold function for each input point, set the input point peak
hold enable bit for each input point.
with peak hold enabled, the peak hold data may be invalid until the peak hold
function is re-enabled.
The alarm function can be used to perform a comparison of the input point
conversion data to specific low and high limits that are stored in the module
memory map. The module sets the alarm bits in the module memory map
when the input point conversion data is outside the specified limits. The mod-
ule can perform low alarming, high alarming, or both.
To use this function for each input point proceed as follows:
1.
2.
Module memory map
Module memory map
Set the input point low alarm limit value and input point high alarm limit
value for each input point.
Set the input point low alarm enable bit and input point high alarm en-
able enable bit for each input point.
19, bits 8-15
25, bits 8-15
22, bits 8-15
28, bits 8-15
9, bits 8-15
22, bits 0-7
28, bits 0-7
9, bits 0-7
location
location
30 to 45
11 to 18
00
Low and high alarm limits
High alarm active flags
Low alarm active flags
High alarm enable bits
Peak hold active flags
Low alarm enable bits
Peak hold enable bits
High alarm flags
Low alarm flags
Peak hold data
Description
Description
Alarm flags
2’s Complement Binary
2’s Complement Binary
BCD -7999 to +7999
BCD -7999 to +7999
-32767 to +32767
-32767 to +32767
Valid data
Valid data
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
Section 4- -3