OS20FB22A1N1 ABB, OS20FB22A1N1 Datasheet - Page 35

no-image

OS20FB22A1N1

Manufacturer Part Number
OS20FB22A1N1
Description
SWITCH,FUSE,FRONT,20A,4P
Manufacturer
ABB
Datasheet

Specifications of OS20FB22A1N1

Fuse Size
A1
No. Of Fuses
1
No. Of Poles
4
Contact Current Ac Max
20A
Contact Voltage Ac Max
690V
Svhc
No SVHC (18-Jun-2010)
Termination Method
Quick Connect
Fuse Size Held
A1
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Auxiliary contacts
Auxiliary contacts for OS 32G...1250
Mounting under the mechanism cover:
The “test” contacts operate in ON- and OFF-positions as well as when the handle is turned to TEST-po-
sition = 45 degrees over the OFF-position. The “test indication” contacts operate only when the handle
is turned to TEST-position. See the function table below. The OA1G10 (N.O.) or OA3G01 (N.C.) auxiliary
contact blocks can be used as standard auxiliary contacts, “test” or “test indication” contacts. The
desired functions are achieved when an auxiliary contact block is installed in a specifi c place shown in
the mounting instruction. In order to activate the “test” and “test indication” features a handle with test
function is required. See the optional handles, page 30.
Function table of OS32G…1250 auxiliary contacts
Maximum number of contact blocks, “Aux./test” contacts and “test indication” contacts, see the table
below. Standard versions include all except for N3-types which are equipped with integrated neutral
through the mechanism.
Maximum number of auxiliary contacts under the mechanism cover
The contact timing: see the chart, pages 63-64.
Mounting on the left side of the switch fuse:
Maximum 8 auxiliary contact blocks (N.O. or N.C.) with the OEA28 module. Units/type = 1 piece.
Types _AU have gold plated contacts for harsh environments and low operating voltages.
Suitable
for
switches
OS32G...1250 1NO
Module for auxiliary contacts
Screw mounting to the left side of the switch OEA28
Performance data for auxiliary contacts
Auxiliary contacts
Ordering information
Handle position
Test
0
I
Pole version
Maximum number of contact blocks
Aux./Test contacts
Test indication contacts
OA1G_, OA3G_
IEC60947-5-1
U
Uimp/[kV]
Pollution
degree
I
Cable size
Maximum fuse
NEMA
Wire size
OA4_
EN61058-1
U
I
Ie
NEMA
M3 Screw connection
th
th
1)
2)
i
i
/[V]
/[A]
6 aux/test contacts and 2 early operation aux./test contacts
4 aux/test contacts and 2 early operation aux./test contacts
Description
1NC
1 NO
1 NC
400V
10A
400V AC
10 (4) A, 10E3
6 (2,5) A, 50E3
10 A, 125-250V AC,
1/4 HP
690
4
3
16
1…2 x 0,75…2,5mm
16A/gG
A600, R300
18 - 14AWG, 1( 2)
Main contacts Aux./Test contacts N.O.
open
open
closed
Protection
degree
IP20
IP20
IP20
IP20
closed
open
closed
2
OS32G…250
Standard
MCB_
IEC60947-5-1
U
I
Ie
NEMA
Ue/[V]
230
400
690
4
4
2
th
Type
OA1G10
OA3G01
OA1G10AU
OA3G01AU
i
AC15
Ie/[A]
6
4
2
690V
10A
24V
110V
220/240V
250V
380/415V
660/690V
A600, 10A, 600VAC
N3
0
0
0
Order number
1SCA022353R4970
1SCA022456R7410
1SCA022436R7910
1SCA022819R5260
1SCA022714R8810
Ue/[V]
24
72
125
250
440
OS315…800
Standard
Test indication contacts N.O.
closed
open
open
8
4
4
DC12
Ie/[A]
10
4
2
0,55
0.1
AC12
10
10
10
N3
4
2
2
P/[W]
240
288
250
138
44
AC15
8
8
6
4
4
2
OS1200…1250
Standard
Delivery Weight
batch
[pcs]
10
10
10
10
1
DC13
Ie/[A]
2
0.8
0.55
0.27
1SCC311013C0201
12
8
4
1)
[kg]
0.03
0.03
0.03
0.03
0.04
DC13
5
1.1
0.55
0.55
P/[W]
48
58
69
68
N3
6
8
2
2)
35