XTPAXLSA EATON CUTLER HAMMER, XTPAXLSA Datasheet - Page 304

Line-Side Adapter

XTPAXLSA

Manufacturer Part Number
XTPAXLSA
Description
Line-Side Adapter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTPAXLSA

For Use With
Eaton Cutler-Hammer XT Series Frame B Manual Motor Protectors
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
34-304
34
Table 34-395. Freedom IEC Open Reversing Combination Motor Controllers (A307 Manual Motor Protector + CE55 IEC 45 mm Reversing Contactor)
Table 34-396. AC and DC Coil Suffixes
AC Coils
DC Coils
FLA
Adjustment
Range
11.0 – 16.0
14.0 – 20.0
17.0 – 22.0
Coil Volts and Hertz
120/60 or 110/50
240/60 or 220/50
480/60 or 440/50
600/60 or 550/50
208/60
277/60
380 – 415/50
24/60, 24/50
120V DC
0.11 – 0.16
0.14 – 0.20
0.18 – 0.25
0.22 – 0.32
0.28 – 0.40
0.35 – 0.50
0.45 – 0.63
0.55 – 0.8
0.7 – 1.0
0.9 – 1.25
1.1 – 1.6
1.4 – 2.0
1.8 – 2.5
2.2 – 3.2
2.8 – 4.0
3.5 – 5.0
4.5 – 6.3
5.5 – 8.0
7.0 – 10.0
9.0 – 12.5
12V DC
24V DC
48V DC
AE357 — Freedom IEC Open Reversing
Combination Motor Controller
Select motor controller by motor Full Load Amperes. Horsepower ratings are for reference only.
Underscore (_) indicates Magnetic Coil Suffix required. See Table 34-396 below.
Mounting plate included.
Add -DIN Modification Code for DIN Rail mounting of contactors with MMP and Wiring Connector Link.
IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
Types AM/AE317/357, AE318/358, AE319/359 Freedom IEC Combination Motor Controllers
Single-Phase
hp Ratings
115V
1
1-1/2
2
1/10
1/8
1/6
1/4
1/3
1/2
1/2
230V
1
1-1/2
2
3
3
3
1/10
1/8
1/6
1/4
1/3
1/2
3/4
Code Suffix
A
B
C
D
E
H
L
T
A1
R1
T1
W1
Three-Phase
hp Ratings
200V
1
1-1/2
2
3
3
5
5
7-1/2
1/4
1/3
1/2
3/4
3/4
230V
1
1
1-1/2
2
3
3
5
7-1/2
7-1/2
1/4
1/3
1/2
1/2
3/4
For use as CMCs in Group Installation
or UL 508 Type F applications.
When Ordering Specify —
Notes —
460V
10
15
15
For more information visit: www.eaton.com
Select required assembled motor
controller by Catalog Number from
Table 34-395 and replace underscore
(_) in the Catalog Number with the
proper Magnetic Coil Code Suffix
Letter from Table 34-396.
All Non-reversing and Reversing
motor controllers are selected based
on the overload current range
required for a given motor. This cur-
rent range is determined from the
motor Full Load Ampere rating and
Motor Service Factor usually found
on the motor nameplate.
Each Combination Motor Controller
Includes: (1) C320FMC11 Front
Mount Auxiliary Contact 1NO/1NC.
The CE55***C* signifies a black
base, A1 & A2 coil terminals at the
bottom and black printing on the
label.
For information on the usage of
Line Side Adapters, see Table 34-
403, Page 34-307.
1
1-1/2
1-1/2
2
3
5
5
7-1/2
7-1/2
1/4
1/2
3/4
3/4
The auxiliary contact is desig-
nated by the S in the following
Catalog Number example:
AE357ANS3A.
575V
10
10
15
20
20
1
1-1/2
1-1/2
2
3
3
5
5
1/4
1/2
1/2
3/4
Manual
Motor
Protector
A307AN
A307BN
A307CN
A307DN
A307EN
A307FN
A307GN
A307HN
A307JN
A307KN
A307LN
A307MN
A307NN
A307PN
A307RN
A307SN
A307TN
A307UN
A307VN
A307WN
A307XN
A307YN
A307ZN
IEC Reversing
Contactor
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55ANSC3_B
CE55BNSC3_B
CE55BNSC3_B
CE55CNSC3_B
CE55CNSC3_B
CE55DNSC3_B
CE55ENSC3_B
CE55FNSC3_B
Instructional Leaflets
See Page 34-300 for Listing.
Note: For more information on Manual
Motor Protectors and Wiring Connector
Links refer to Pages 34-294 – 34-299. For
Freedom Contactors refer to Pages 34-261 –
34-289.
Accessories . . . . . . . . . . . . . . . . . . . . . Page 34-307
Dimensions . . . . . . . . . . . . . . . . . . . . . . Page 34-308
Discount Symbol . . . . . . . . . . . . . . . . . 1CD7
For motors with service factors less
than 1.15, multiply the motor FLA by
.92 to select the appropriate motor
controller. Example: For a motor
having FLA of 6.4A and a service
factor of 1.0 (6.4A x .92 = 5.88A)
select Catalog Number
AE357TNS3_.
For motors with service factor of
1.15 or greater, use motor name-
plate Full Load Amperes to select
the appropriate motor controller.
Example: For motor having FLA of
6.4A and service factor of 1.15,
select Catalog Number
AE357UNS3_.
Catalog
Number
AE357ANS3_
AE357BNS3_
AE357CNS3_
AE357DNS3_
AE357ENS3_
AE357FNS3_
AE357GNS3_
AE357HNS3_
AE357JNS3_
AE357KNS3_
AE357LNS3_
AE357MNS3_
AE357NNS3_
AE357PNS3_
AE357RNS3_
AE357SNS3_
AE357TNS3_
AE357UNS3_
AE357VNS3_
AE357WNS3_
AE357XNS3_
AE357YNS3_
AE357ZNS3_
Price
U.S. $
AC Coil
CA08102001E
March 2009
DC Coil

Related parts for XTPAXLSA