70-841-025 Emerson Network Power, 70-841-025 Datasheet

no-image

70-841-025

Manufacturer Part Number
70-841-025
Description
LPS100-M CONNECTOR KIT
Manufacturer
Emerson Network Power
Series
LPS100-Mr
Datasheet

Specifications of 70-841-025

Accessory Type
Connector Kit
For Use With
454-1289 - POWER SUPPLY AC/DC 5V OUT454-1470 - POWER SUP 12V 150W 2"X4" MED&ITE454-1471 - POWER SUP 15V 150W 2"X4" MED&ITE454-1473 - POWER SUP 48V 150W 2"X4" MED&ITE454-1472 - POWER SUP 24V 150W 2"X4" MED&ITE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
LPS100-M Series
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
454-1365
Safety
• TUV
• UL
• cULus
• CB
• CE
• CQC
Total Power:
Input Voltage:
# of Outputs:
Special Features
• Medical and ITE safeties
• Active power factor correction
• 2” x 4” footprint
• Less than 1U high
• EN61000-3-2 compliant
• Remote sense
• Power fail
• Adjustable main output
• Built-in Class B EMI filter
• Overvoltage protection
• Overload protection
• Thermal overload protection
• Isolated12 V Fan output
• LPX50 Enclosure kit available
LPS100-M Series
150 Watts
60950, 60601-1
60950, 60601-1
60950, 60601-1
Certificate & report
Mark (LVD)
Mark
80 - 150 Watts
90 - 264 Vac
Single
Electrical Specifications
Input
Input ra nge:
Frequency:
Inrush current:
Efficiency:
EMI/RFI:
Safety ground
leakage current:
Output
Maximum power:
Adjustment range:
Fan output:
Hold-up time:
Overload protection:
Overvoltage protection: 15-35% above nominal output
Logical Control
Power failure:
Remote sense:
90 - 264 Vac; 120 - 300 Vdc
47-63 Hz
50 A max., cold start @ 25 °C
88% typical at full load
FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
275 µA @ 50/60 Hz, 264 Vac input
100 W for convection (80 W for LPS102-M);
150 W with 30 CFM forced air (120 W for LPS102-M)
± 10% minimum on the main outputs
12 V @ 1 A isolated, ± 10%
10 ms @ 150 W load, 120 Vac input
Short circuit protection on all outputs. Case overload
protected @ 110-160% above rating
Open collector logic signal goes high 100-500 msec after main output; it
goes low at least 6 msec before loss of regulation
Compensates for 0.5 V lead drop min. Will operate without remote sense
connected. Reverse connection protected.
Embedded Power for
Business-Critical Continuity
Rev. 03.30.10_29
LPS100-M Series
1 of 3

Related parts for 70-841-025

70-841-025 Summary of contents

Page 1

LPS100-M Series 150 Watts Total Power 150 Watts Input Voltage 264 Vac # of Outputs: Single Special Features • Medical and ITE safeties • Active power factor correction • 2” x 4” footprint • Less than ...

Page 2

... Environmental Specifications Operating temperature: 0° °C ambient derate each output as 2.5% per degree from 50° °C. -20 °C start up Storage temperature: -40 °C to +85 °C Electromagnetic Designed to meet EN61000-4; susceptibility: -2, -3, -4, -5, -6, -8, -11 Level 3 Humidity: Operating; non-condensing 10% to 95% RH Vibration: IEC68-2-6 to the levels of IEC721-3-2 MTBF calculated: 534,000 hours at full load and 25 ° ...

Page 3

... Landwin P/N: 2640S04A0, Pins: 2543T011P Fan: (SK5): Molex P/N: 22-01-1042, Pins: 08-70-0049 or Landwin: P/N: 2510S04A0, Pins: 2543T011P Emerson Network Power Connector Kit #70-841-025, includes all of the above Embedded Power for Business-Critical Continuity Americas 5810 Van Allen Way Ripple Carlsbad, CA 92008 ...

Related keywords