NPS48-M Emerson Network Power, NPS48-M Datasheet

POWER SUP MED&ITE 48V 45W 2"X4"

NPS48-M

Manufacturer Part Number
NPS48-M
Description
POWER SUP MED&ITE 48V 45W 2"X4"
Manufacturer
Emerson Network Power
Series
NPS40-Mr
Datasheet

Specifications of NPS48-M

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
60W
Applications
Medical
Power Supply Type
Switching (Open Frame)
Voltage - Input
90 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 940mA
Size / Dimension
4" L x 2" W x 1" H (101.6mm x 50.8mm x 25.4mm)
Power (watts) - Rated
45W
Operating Temperature
0°C ~ 80°C
Efficiency
87%
Approvals
CB, CE, CSA, NEMKO, TUV, UL
Line Regulation
±2%
Load Regulation
±2%
Commercial/medical
Both
Output Power Rating
40 W, 60 W
Input Voltage
90 VAC to 264 VAC, 127 VDC to 300 VDC
Output Voltage (channel 1)
48 V
Output Current (channel 1)
0.94 A
Mounting Style
Chassis
Dimensions
2 in L x 4 in W x 0.86 in H
Open Frame/enclosed
Open Frame
Output Type
DC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
NPS40-M Series
60 Watts
Special Features
• Medical and ITE Safety Approvals
• Universal input
• Less than 1U high
• 2” x 4” footprint
• Remote sense
• Overload and short circuit
• Adjustable output voltage
• High efficiency
• High MTBF
• Built in EMI filter
• International Efficiency Level V,
• Less than 300 mW no-load
• 0˚C to +80˚C operation
• Input power < 74 watts
• Complies with EN61000 -3-2
• UL Class I approved
• LPX50 enclosure kit available
Safety
Total Power:
Input Voltage:
# of Outputs:
protection
(CISPR 22 Class B)
Energy Star 2.0 & CeC compliant
(except NPS42-M)
power consumption
TUV: 60950, 60601-1
UL:
CSA: 60950, 60601-1
NEMKO: 60950, 60601-1
CB:
CE:
60950, 60601-1
Mark (LVD)
Certificate and report
45 - 60 Watts
90 - 264 VAC
127 - 300 VDC
Single
Electrical Specifications
Input
Input range:
Frequency:
Inrush current:
Input power:
Efficiency:
EMI/RFI:
Safety ground leakage
current:
Output
Maximum power:
Adjustment range:
Hold-up time:
Overload protection:
Overvoltage protection: 30-50% above nominal output
Remote sense:
90 - 264 VAC (wide range) 127-300 Vdc
47-440 Hz
< 50 A peak @ 230 VAC, cold start @ 25° C
< 74 Watts
87% average (as per Energy Star 2.0 standard)
FCC Class B conducted; CISPR 22 Class B conducted; EN55022 Class B
conducted, VDE0878PT3 Class B conducted
275uA @ 50/60 Hz; 264 VAC input
45W for convection (40W for NPS42-M). 60 W with 200LFM forced air
(55 Watts for NPS42-M)
±20% minimum
10/ 2 0 ms 115/230 VAC input line
Short circuit protection on all outputs. Case overload protected @
110-160% of normal rating
Compensated for 0.5 V lead drop max. Will operate without remote sense
connected. Reverse connection protected.
Embedded Power for
Business-Critical Continuity
Rev. 9.15.09_163
NPS40-M Series
1 of 3

Related parts for NPS48-M

NPS48-M Summary of contents

Page 1

NPS40-M Series 60 Watts Total Power Watts Input Voltage 264 VAC 127 - 300 VDC # of Outputs: Single Special Features • Medical and ITE Safety Approvals • Universal input • Less than 1U high • 2” x 4” footprint • Remote sense • Overload and short circuit protection • Adjustable output voltage • High efficiency • High MTBF • Built in EMI filter (CISPR 22 Class B) • International Efficiency Level V, Energy Star 2.0 & CeC compliant (except NPS42-M) • Less than 300 mW no-load power consumption • 0˚C to +80˚C operation • Input power < 74 watts • Complies with EN61000 ...

Page 2

Environmental Specifications Operating temperature: 0° °C ambient derate each output as 2.5% per degree from 50° °C. -20 °C start up Storage temperature: -45 °C to +85 °C Electromagnetic susceptibility: Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Humidity: Operating; non-condensing 10% to 90% RH Vibration: IEC68-2-6 to the levels of IEC721-3-2 MTBF demonstrated: > 550,000 hours at full load and 25 °C ambient conditions Mechanical Drawing BARCODE M1 GND TAB (CN1) PIN 1 PIN 3 INPUT CONNECTOR (SK1) 0.16” (4.0) MOUNTING HOLE (4 PLACES) 0.197” (5.0) MINIMUM STANDOFF HEIGHT 4.00" (101.6) 3.73" ...

Page 3

... West Midlands, DY5 1LX United Kingdom ±2% 480 mV Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355 Asia (HK) 14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888 NPS48-M Line For global contact, visit: Neutral www.PowerConversion.com techsupport.embeddedpower +48 V @emerson.com +48 V Common While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Common Network Power assumes no responsibility, and disclaims ...