2320018 Phoenix Contact, 2320018 Datasheet - Page 10

CONVERTER DC-DC 12-24/5-15VDC 2A

2320018

Manufacturer Part Number
2320018
Description
CONVERTER DC-DC 12-24/5-15VDC 2A
Manufacturer
Phoenix Contact
Series
Minir
Type
Isolatedr
Datasheet

Specifications of 2320018

Output
12V
Number Of Outputs
1
Power (watts)
24W
Mounting Type
DIN Rail
Voltage - Input
12 ~ 24V
Package / Case
Module
1st Output
12 VDC @ 2A
Size / Dimension
4.21" L x 0.89" W x 3.90" H (107mm x 22.5mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
24W
Efficiency
88%
Approvals
cUL, EN, UL, VDE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
MINI-PS- 12- 24DC/ 5-15DC/2
Active signal output
The DC output signal in normal operation of the power supply
unit (U
> 0.9 x U
) is between the "DC OK" and "-"
OUT
N
connection terminal blocks and can carry a maximum of
20mA. By switching from "active high" to "low", the DC OK
+ - -
signal output signalizes when the output voltage is fallen short
of by more than 10%.
The DC OK signal is decoupled from the power output. It is
thus not possible for devices connected in parallel to act as an
DC OK
external power supply.
13
Function
Thermal behavior
The device can supply a nominal output current of 2 A with
ambient temperatures of up to 60°C. For ambient
I
temperatures above 60°C, the output current must be
N
reduced by 2.5% per Kelvin increase in temperature. From
70°C onwards or in the case of thermal overload, the device
reduces the output capacity for its own protection, and returns
to normal operation when it has cooled down.
0
-25
20
40
60
Ambient temperature [°C]
Parallel operation
Devices of the same type can be connected in parallel to
increase both redundancy and power. By default upon
delivery, no further adjustments are required.
If the output voltage is adjusted, a uniform distribution of
power is guaranteed by setting all parallel operated power
supply units to exactly the same output voltage.
To ensure symmetrical current distribution we recommend
that all cable connections from the power supply unit to the
busbar are the same length and have the same cross section.
Depending on the system, for parallel connection of more
than two power supplies a protective circuit should be
installed at each individual device output (e.g., decoupling
diode, DC fuse or circuit breaker). This prevents high return
currents in the event of a secondary device fault.
10
104346_en_00
PHOENIX CONTACT