2866983 Phoenix Contact, 2866983 Datasheet - Page 9

POWER SUPPLY 1.5A 24VDC

2866983

Manufacturer Part Number
2866983
Description
POWER SUPPLY 1.5A 24VDC
Manufacturer
Phoenix Contact
Series
Minir
Type
Industrialr
Datasheets

Specifications of 2866983

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
36W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 1.5A
Size / Dimension
3.74" L x 1.38" W x 3.90" H (95mm x 35mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
36W
Efficiency
84%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
36 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
1.5 A
Mounting Style
DIN Rail
Interface
Ethernet Modem
Phoenix Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Standards
TBR21, TIA-968-A, CS-03 for Europe, USA, and Canada
Voltage, Supply
85-264 VAC
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 1.5 A
Power, Output
6.5 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2136
MINI-SYS-PS-100-240AC/24DC/1.5
102050_01_en
Output
They are connected using the "24 V" and "0 V" screw connections on the screw connection of the DC output and via the
DIN rail connector.
Protection of the secondary side
The device is electronically protected against short circuit and idling. In the event of a malfunction, the output voltage is
limited to 30 V DC.
Signaling
For function monitoring, there is the floating DC OK switching output and the DC OK LED.
DC OK LED
Floating DC OK output
Meaning
max.
30 V AC/DC, 1 A
Output 24 V DC
DC OK
2
State 1
Closed
Normal operation of the power supply
(U
ON
OUT
> 21.5 V)
Floating contact
The floating signal contact opens and signalizes a drop in the
output voltage of 21.5 V. Signals and ohmic loads of up to
30 V and currents of up to 1 A can be connected. For heavily
inductive loads such as a relay, a suitable protection circuit
(e.g. damping diode) is necessary.
Make sure that all output lines are dimen-
sioned according to the maximum output cur-
rent or are separately protected. The cables on
the secondary side must have sufficiently large
cross sections in order to keep the voltage
drops on the lines as low as possible.
MINI-SYS-PS-100-240AC/24DC/1.5
State 2
OFF
Open
1. The output voltage is less than
21.5 V. There is a secondary consumer
short circuit or overload.
2. There is no input voltage or there is a
device fault.
PHOENIX CONTACT