2866983 Phoenix Contact, 2866983 Datasheet - Page 10

POWER SUPPLY 1.5A 24VDC

2866983

Manufacturer Part Number
2866983
Description
POWER SUPPLY 1.5A 24VDC
Manufacturer
Phoenix Contact
Series
Minir
Type
Industrialr
Datasheets

Specifications of 2866983

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
36W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 1.5A
Size / Dimension
3.74" L x 1.38" W x 3.90" H (95mm x 35mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
36W
Efficiency
84%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
36 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
1.5 A
Mounting Style
DIN Rail
Interface
Ethernet Modem
Phoenix Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Standards
TBR21, TIA-968-A, CS-03 for Europe, USA, and Canada
Voltage, Supply
85-264 VAC
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 1.5 A
Power, Output
6.5 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2136
MINI-SYS-PS-100-240AC/24DC/1.5
102050_01_en
Function
U
[V]
OUT
U
N
I
I
BOOST
N
0
0
< 60 °C
Ambient temperature [°C]
20
I
N
< 40 °C
40
I
BOOST
60
I
[A]
OUT
Output characteristic curve
The device can supply a nominal output current of 1.5 A with
ambient temperatures of up to 60°C. At an ambient temper-
ature of up to 40°C, the device supplies a continuous output
current of 2 A. At temperatures up to 60°C, the POWER
BOOST provides a transient output current of 2 A for a few
minutes. In the event of a higher load, the operating point fol-
lows the U/I characteristic curve depicted in the figure.
In the case of overload or short-circuit, the full output current
I
the device does not switch off. As soon as the overload or
short-circuit is no longer present, the full secondary voltage
is once again available.
The U/I characteristic curve ensures that both heavily capac-
itive loads and devices with DC/DC converters in the primary
circuit can be fed without problems using MINI POWER.
Downstream fuses are triggered reliably. Selectivity in the
design of your system is guaranteed at all times.
U
I
I
Thermal behavior
With an ambient temperature of up to +60°C, the device sup-
plies the continuous output current of I
ent temperatures above +60°C, the output current must be
reduced by 2.5% per Kelvin increase in temperature. The de-
vice does not switch off at ambient temperatures of +70°C or
thermal overload. The output capacity is reduced as far as
necessary to provide device protection. After it has cooled
down, the output capacity is increased again.
BOOST
N
BOOST
N
= 1.5 A
= 24 V
is supplied permanently with reduced output voltage,
= 2 A
MINI-SYS-PS-100-240AC/24DC/1.5
N
PHOENIX CONTACT
. In the case of ambi-
10

Related parts for 2866983