2866983 Phoenix Contact, 2866983 Datasheet - Page 4

POWER SUPPLY 1.5A 24VDC

2866983

Manufacturer Part Number
2866983
Description
POWER SUPPLY 1.5A 24VDC
Manufacturer
Phoenix Contact
Series
Minir
Type
Industrialr
Datasheets

Specifications of 2866983

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
36W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 1.5A
Size / Dimension
3.74" L x 1.38" W x 3.90" H (95mm x 35mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
36W
Efficiency
84%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
36 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
1.5 A
Mounting Style
DIN Rail
Interface
Ethernet Modem
Phoenix Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Standards
TBR21, TIA-968-A, CS-03 for Europe, USA, and Canada
Voltage, Supply
85-264 VAC
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 1.5 A
Power, Output
6.5 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2136
MINI-SYS-PS-100-240AC/24DC/1.5
102050_01_en
Conformance with EMC directive 89/336/EEC
Immunity to interference in acc. with EN 61000-6-2
Discharge of static electricity in acc. with EN 61000-4-2
Electromagnetic HF field in acc. with EN 61000-4-3
Fast transients (burst) in acc. with EN 61000-4-4
Surge voltage capacities (surge) in acc. with EN 61000-4-5
Conducted disturbance in acc. with EN 61000-4-6
Voltage dips in acc. with EN 61000-4-11
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011
Emitted radio interference in acc. with EN 55011
Note:
Criterion A: Normal operating behavior within the defined limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself
EN 55011 corresponds to CISPR11 / EN 55022 corresponds to CISPR22
EN 61000 corresponds to IEC 1000
Housing
Contact discharge
Discharge in air
Comments
Housing
Frequency range
Field intensity
Comments
Input
Output
Signal
Comments
Input
Output
Signal
Comments
Input/Output/Signal
Frequency range
Voltage
Comments
Input
Comments
Level 3
6 kV
8 kV
Criterion B
Level 3
80 MHz ... 2 GHz
10 V/m
Criterion A
4 kV (level 4 - asymmetrical: conductor to ground)
2 kV (level 3 - asymmetrical: conductor to ground)
1 kV (level 2 - asymmetrical: conductor to ground)
Criterion B
4 kV (level 4 - asymmetrical: conductor to ground)
2 kV (level 4 - symmetrical: conductor to conductor)
0.5 kV (level 1 - asymmetrical: conductor to ground)
0.5 kV (level 1 - symmetrical: conductor to conductor)
0.5 kV (level 1 - asymmetrical: conductor to ground)
Criterion B
Level 3 - asymmetrical
0.15 MHz ... 80 MHz
10 V
Criterion A
(mains buffering > 20 ms)
Criterion B
EN 55011 (EN 55022) Class B, area of application: Industry and residential
EN 55011 (EN 55022) Class B, area of application: Industry and residential
MINI-SYS-PS-100-240AC/24DC/1.5
PHOENIX CONTACT
4