f4-08da-2 Automation Direct, f4-08da-2 Datasheet

no-image

f4-08da-2

Manufacturer Part Number
f4-08da-2
Description
Analog Output Modules
Manufacturer
Automation Direct
Datasheet
6–80
Number of Channels
F4-08DA-2
F4-16DA-2
Output Range
Resolution
Output Type
External Load Resistance
Crosstalk
Linearity Error (End-to-End)
and Relative Accuracy
Full Scale Calibration Error
(Offset Error Included)
Offset Calibration Error
Maximum Inaccuracy
1kW- -10kW
1kW- -10k W
1kW - -10kW
F4-08DA-2 8-Channel Analog Voltage Output <--->
CH16
F4-16DA-2 16-Channel Analog Voltage Output <--->
CH2
CH1
Typical Us er Wiring
PLC Products
(s ame)
Voltage
Voltage
Voltage
Output
Output
Output
21.6 - - 26.4 VDC
Us er S upply
+
275mA
S ee NOTE 1
- -
8, single ended (one common)
16, single ended (one common)
0-5VDC, 0-10VDC
12 bit (1 to 4095)
Voltage Sourcing 10mA max.
1K max./10K min.
(example: 10volts@ 1K = 10mA load)
-70dB, ± 1 count maximum
± 1count maximum (10VDC at 25°C)
± 6 counts max. (10VDC at 25°C)
± 3 counts max. (0VDC at 25°C)
±0.2% @ 77°F (25°C)
±0.4% @ 32 to 140°F (0 to 60°C)
CH12
CH14
CH10
CH16
CH2
CH4
CH6
CH8
0V
0V
CH13
CH15
CH11
CH1
CH3
CH5
CH7
CH9
0V
24V
0- -10 V S ourcing
Internal module circuitry
(s ame)
0- -10 V S ourcing
(s ame)
Converter
Conversion Time
Digital Output Points
Required
Power Budget Require
Terminal Type (included)
External Power Supply
Accuracy vs. Temperature
Operating Temperature
Storage Temperature
Relative Humidity
Environmental Air
Vibration
Shock
Noise Immunity
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4,096).
NOTE 1: Shields should be connected to the 0V of the User Power Supply at the module terminal block.
Internal
DC/DC
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
D/A
24 VDC 275mA
CH10
CH12
CH14
CH16
F 4- -16DA- -2
ANALOG
0- -10VDC
CH2
CH4
CH6
CH8
+V
+V
+V
+V
+V
+V
+V
+V
0V
0- -5VDC
--
CH11
CH13
CH15
CH1
CH3
CH5
CH7
CH9
+V
+V
+V
+V
+V
+V
+V
+V
0V
+
400µs maximum, for full scale change
4.5 to 9ms for digital out to analog out
F4-08DA-2
16 (Y) output points 12 bits binary data, 3 bits
channel select ,1 bit output enable)
F4-16DA-2
32 (Y) output points (two sets each of 12 bits
binary data, 3 bits channel select ,1 bit output
enable)
80mA @ 5VDC (base power)
Removable (D4-16IOCON)
21.6-26.4VDC, 150mA, class 2
± 57 ppm/°C full scale calibration range
(including maximum offset change, 2 counts)
32° to 140°F (0 to 60°C)
-4 to 158°F (-20 to 70°C)
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
NEMA ICS3-304
OUTP UT
1 - 8 0 0 - 6 3 3 - 0 4 0 5

Related parts for f4-08da-2

Related keywords