F4-04ADS Automation Direct, F4-04ADS Datasheet

no-image

F4-04ADS

Manufacturer Part Number
F4-04ADS
Description
Analog Input Modules
Manufacturer
Automation Direct
Datasheet
w w w . a u t o m a t i o n d i r e c t . c o m / d l 4 0 5
Number of Channels
Input Ranges
Channels Individually
Configurable
Resolution
Conversion Method
Input Type
Max. Common Mode Voltage
Noise Rejection Ratio
Active Low-pass Filtering
Input Impedance
Absolute Maximum Ratings
Conversion Time
Linearity Error:
Full Scale Calibration Error
Offset Calibration Error
F4-04ADS 4-Channel Isolated Analog Input <--->
4-wire 4-20mA
2-wire 4-20mA
Transmitter
Transmitter
Voltage Transmitter
CH3
CH4
CH1
unipolar
bipolar
Not used
CH2
User Supply
4
0-5V, 0-10V, 1-5V, ±5V, ±10V
0-20mA, 4-20mA
Yes
12 bit (1 to 4,096)
Successive Approximation
Differential
± 750V peak continuous transformer isolation
Common mode: -100dB @ 60Hz
-3dB at 20Hz, -12 dB per octave
250 ± 0.1%, 1/2W current input
200K voltage point
-45mA to + 45mA, current input
± 100V voltage input
1ms per selected channel
± 1 count (0.025% of full scale) max.
± 2 counts (0.025% of full scale) max.
± 8 counts maximum (V
± 8 counts maximum (V
in
in
= 20mA)
= 4mA)
PLC Update Rate
Digital Input Points Required
Accuracy vs Temperature
Terminal Type (included)
Base Power Required 5V
External Power Supply
Recommended Fuse
Operating Temperature
Accuracy vs. Temperature
Storage Temperature
Relative Humidity
Environmental Air
Vibration
Shock
Noise Immunity
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4,096).
NOTE 1: Shields should be grounded at signal source
NOTE 2: Unused channels should have V & C & R of the channels jumpered
1 channel per scan
16 (X) input points (12 binary data bits, 4
active channel indicator bits)
± 100 ppm/ÞC maximum full scale (including
maximum offset)
Removable (D4-16IOCON)
270mA
24VDC, ± 10%, 120mA, class 2
0.032 A, Series 217 fast-acting, current inputs
32° to 140°F (0 to 60°C)
±100 ppm /°C maximum full scale
(including maximum offset)
-4 to 158°F (-20 to 70°C)
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
NEMA ICS3-304
PLC Products
6–73
PLC
Overview
DL05/06
PLC
DL105
PLC
DL205
PLC
DL305
PLC
DL405
PLC
Field I/O
Software
C-more
HMIs
Other HMI
AC Drives
Motors
Steppers/
Servos
Motor
Controls
Proximity
Sensors
Photo
Sensors
Limit
Switches
Encoders
Current
Sensors
Pushbuttons/
Lights
Process
Relays/
Timers
Comm.
TB’s &
Wiring
Power
Circuit
Protection
Enclosures
Appendix
Part Index

Related parts for F4-04ADS

Related keywords