f4-08thm Automation Direct, f4-08thm Datasheet

no-image

f4-08thm

Manufacturer Part Number
f4-08thm
Description
Temperature Input Modules
Manufacturer
Automation Direct
Datasheet
Temperature Input Modules
w w w . a u t o m a t i o n d i r e c t . c o m / d l 4 0 5
General Specifications
Number of Channels
Common Mode Range
Common Mode Rejection
Input Impedance
Absolute Maximum Ratings
Accuracy vs. Temperature
PLC Update Rate
Digital Inputs
Input Points Required
Terminal Type (included)
External Power Supply
Power Budget
Requirements
Operating Temperature
Storage Temperature
Relative Humidity
Environmental Air
Vibration
Shock
Noise Immunity
24VDC ±10% Class 2
CH1
CH3
CH4
CH5
CH8
See note
User Supply
Examples of differential
Examples of grounded
Thermocouple wiring
Thermocouple wiring
Thermocouple Input Wiring Diagram
8, differential
± 5VDC
90dB min. @ DC, 150dB min. @ 50/60Hz.
1M
Fault-protected inputs to ± 50VDC
± 5ppm/°C maximum full scale calibration
(including maximum offset change)
8 channels per scan max
16 binary data bits, 2 channel ID bits, 4
diagnostic bits
32 points (X) input module
Removable (D4-16IOCON)
60mA maximum, 18 to 26.4VDC
110mA max., 5VDC (supplied to base)
0° to 60°C (32° to 140°F)
-20° to 70°C (-4° to 158°F)
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
NEMA ICS3-304
24V+
Com
Com
Com
–3
– 4
–5
– 6
–8
–1
+1
–2
+2
+3
+4
+5
+6
–7
+7
+8
0V
Internal Module Wiring
Analog
Switch
F4-08THM 8-Channel Thermocouple Input <--->
A/D
F4–08THM
TEMPERATURE
24V @60mA
COM
CH1–
CH1+
CH2–
CH2+
CH3–
CH3+
CH4–
CH4+
COM
CH5–
CH5+
CH6–
CH6+
CH7–
CH7+
CH8–
CH8+
COM
Thermocouple Specifications
Input Ranges*
Display Resolution
Cold Junction Compensation
Conversion Time
Warm-Up Time
Linearity Error (End to End)
Maximum Inaccuracy
Voltage Input Specifications
Voltage Ranges
Resolution
Full Scale Calibration Error
(Offset error Included)
Offset Calibration Error
Linearity Error (End to End)
Maximum Inaccuracy
NOTE 1: Terminate shields at the respective signal source
NOTE 2: Leave unused channels open (no connection)
*Thermocouple type is selected by setting internal jumpers
NOTE 3: This module is not compatible with the ZIP Link wiring system.
THERMOCOUPLE
24V
0V
INPUT
Note 3: When using 0-156mV and 5V ranges, connect CH-
terminal to Com or 0V terminal to ensure common mode
range acceptance. Also, connect any unused channels
to Com or 0V terminal.
24VDC ±10% Class 2
Type J
Type E
Type K
Type R
Type S
Type T
Type B
Type N
Type C
± 0.1°C or ± 0.1°F
Automatic
100ms per channel
30 minutes typically ± 1°C repeatability
± .05°C maximum, ± .01°C typical
± 3°C (excluding thermocouple error)
0-5V, ± 5V, 0-156.25mV, ± 156.25mVDC
16 bit (1 in 65535)
± 13 counts typical, ± 33 maximum
± 1 count maximum, @ 0V input
± 1 count maximum
± 02% @ 25°C (77°F)
User Supply
Voltage Input Wiring Diagram
Voltage
Transmitter
Voltage
Transmitter
Voltage
Transmitter
-210 to 1000°C
-150 to 1372°C
-230 to 400°C
529 to 1820°C
-70 to 1300°C
-190 to 760°C
65 to 2320°C
PLC Products
65 to 1768°C
65 to 1768°C
24V+
Com
Com
Com
–1
+1
–2
+2
–3
+3
– 4
+4
–5
+5
– 6
+6
–7
+7
–8
+8
0V
Internal Module Wiring
-310 to 1400°F
-346 to 1832°F
-238 to 2502°F
149 to 3214°F
149 to 3214°F
-382 to 752°F
984 to 3308°F
-94 to 2372°F
149 to 4208°F
e7–85
Analog
Switch
A/D
Company
Info.
PLCs
Field I/O
Software
C-more &
other HMI
AC Drives
AC Motors
Power
Transmiss.
Steppers/
Servos
Motor
Controls
Proximity
Sensors
Photo
Sensors
Limit
Switches
Encoders
Current
Sensors
Pressure
Sensors
Temp.
Sensors
Pushbuttons/
Lights
Process
Relays/
Timers
Comm.
Terminal
Blocks &
Wiring
Power
Circuit
Protection
Enclosures
Tools
Pneumatics
Appendix
Part Index

Related parts for f4-08thm

f4-08thm Summary of contents

Page 1

... Temperature Input Modules F4-08THM 8-Channel Thermocouple Input <---> General Specifications Number of Channels 8, differential Common Mode Range ± 5VDC Common Mode Rejection 90dB min. @ DC, 150dB min. @ 50/60Hz. Input Impedance 1M Absolute Maximum Ratings Fault-protected inputs to ± 50VDC ± 5ppm/°C maximum full scale calibration Accuracy vs ...

Page 2

... Temperature Input Modules F4-08THM-n 8-Channel Thermocouple Input When you order the module, replace the "n" with the type of Thermocouple needed. For example, to order a Type J thermocouple module, order part number F4-08THM-J or part number F4-08THM-K for a Type K module. Number of channels 8, differential inputs Type B 529/1820° ...

Page 3

... F4-08RTD 8-Channel RTD Input <---> Number of Channels 8 Type Pt100: -200/850°C, -328/1562°F Type Pt1000: -200/595°C, Input Ranges -328/1103°F Type jPT100: -38/450°C, -36/842°F Type CU-10/25W: -200/260°C, -328/500°F Resolution 16 bit (1 in 65535) Input Impedance 27K Display Resolution ± ...

Related keywords