CV500CN228 Omron, CV500CN228 Datasheet - Page 118

no-image

CV500CN228

Manufacturer Part Number
CV500CN228
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500CN228

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
C500-LK101-(P)V1
C500-LK203
I/O port
Synchronization Internal
Termination
resistance
CTS
5 V supply
ON
OFF
RS-422
RS-232C
External
OFF
ON
0 V
External
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Baud rate
SW1
SW2
19,200 bps
9,600 bps
4,800 bps
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
CTS setting selector switch
Always set to the 0 V (ON) position.
Termination resistance ON/OFF switch.
Set ON when using an RS-422 cable.
Note: The termination resistance must also be
Baud rate
19,200 bps
DIP switch SW1: Unit # setting
DIP switch SW2: Baud rate, 1-to-1/1-to-N, instruction level setting
9,600 bps
4,800 bps
SW1
SW2
turned ON at the Link Adaptor
1 2 3 4 5 6 7 8
0 0 0 0 0
1 2 3 4 5 6 7 8
0 0 1 0
1 0 1 0
0 1 1 0
Set ON (5 V supply ON) when connecting through Optical Modules.
Set OFF when connecting through the Link Adaptor.
I/O port selector switch
When connecting to the RS-232C connector, set to RS-232C.
When connecting to the RS-422 connector, set to RS-422.
DIP switch SW1: Unit #, parity, transfer code setting
Synchronization setting selector switch
Set to Internal.
DIP switch SW2: Baud rate, 1-to-1/1-to-N, instruction level setting
1 2 3 4 5 6 7 8
0 0 1 0
1 0 1 0
0 1 1 0
1 2 3 4 5 6 7 8
0 0 0 0 0
0
1
1
1
1
0
0
0
0 0
Set to 0.
Instruction level setting
Set to enable levels 1, 2, 3
1-to-1/1-to-N setting
Set to 1-to-N.
1
1
1
1
0
0
Parity, transfer code setting.
Unit # setting.
Set to 0.
Instruction level setting
Set to enable levels 1, 2, 3
1-to-1/1-to-N setting
Set to 1-to-N.
Appendix E

Related parts for CV500CN228