H3CR-A8E AC100-240/DC100-125 Omron, H3CR-A8E AC100-240/DC100-125 Datasheet - Page 9

RELAY ANALOG SET DPDT 8PIN

H3CR-A8E AC100-240/DC100-125

Manufacturer Part Number
H3CR-A8E AC100-240/DC100-125
Description
RELAY ANALOG SET DPDT 8PIN
Manufacturer
Omron
Series
H3CR-Ar

Specifications of H3CR-A8E AC100-240/DC100-125

Mounting Type
Socket
Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 300 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
100 ~ 240VAC, 100 ~ 125VDC
Termination Style
8 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Timing Range
0.05 s to 300 Hrs
Supply Voltage
100 VAC to 240 VAC, 100 VDC to 125 VDC
Accuracy
+/- 0.2 %
Current Rating (max)
5 A
Display Type
Hand Dial
Operating Temperature Range
- 10 C to + 55 C
Time Range
0.05 Sec. To 300 Hr.
Supply Voltage Ac, Min
100VAC
No. Of Timing Functions
4
Body Material
94B3297
No. Of Pins
8
Supply Voltage Ac, Max
240VAC
Load Current Rms Max
5A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
H3CR-A8EAC100-240/DC100-125
H3CRA8EAC100240DC100125
H3CRA8EAC100240DC100125
Q3619148
■ Input Connections
H3CR-A/-AS
The inputs of the H3CR-A/-AS are no-voltage (short-circuit or open) inputs.
No-voltage Inputs
No-contact Input
(Connection to NPN open
collector output sensor.)
Sensor
No-voltage Input Signal Levels
12 to 24 VDC
(sensor power supply)
No-contact
input
Contact
input
Operates with transistor ON
1. Short-circuit level
Transistor ON
Residual voltage: 1 V max.
Impedance when ON: 1 kΩ max.
2. Open level
Transistor OFF
Impedance when OFF: 100 kΩ min.
Use contacts which can
adequately switch 0.1 mA at 5 V
+
2
Timer
5
6
7
DC power
supply
Input (0 V)
Gate
Start
Reset
Contact Input
Operates with relay ON
2
Timer
5
6
7
Input (0 V)
Gate
Start
Reset
Sensor
No-contact Input
(Connection to a voltage
output sensor.)
12 to 24 VDC
(sensor power supply)
Operates with transistor ON
+
2
Timer
DC power
supply
5
6
7
Input (0 V)
Gate
Start
Reset
H3CR-A
9

Related parts for H3CR-A8E AC100-240/DC100-125