H3CA-A Omron, H3CA-A Datasheet - Page 9

RELAY TIMER SSR SPDT 24V

H3CA-A

Manufacturer Part Number
H3CA-A
Description
RELAY TIMER SSR SPDT 24V
Manufacturer
Omron
Series
H3CAr
Datasheet

Specifications of H3CA-A

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.1 Sec ~ 9990 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
3A @ 250VAC
Voltage - Supply
24 ~ 240VAC, 12 ~ 240VDC
Mounting Type
Socket
Termination Style
11 Pin Socketable
Timing Adjustment Method
Thumbwheel Switches
Timing Initiate Method
Input Voltage
Timing Range
0.1 s to 9990 Hrs
Supply Voltage
24 V to 240 V
Accuracy
+/- 0.3 %, - 0.05 s
Current Rating (max)
3 A
Display Type
LED Backlight
Operating Temperature Range
- 10 C to + 55 C
Output Current
3A
Supply Voltage Max
240VAC
Time Range Max
9990h
Switch Function
SPDT
Time Range Min
0.1s
No. Of Digits / Alpha
3
Supply Voltage Min
24VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
H3CA-A
H3CAA
Z2359
Mounting Track (Meets DIN EN50022)
Protective Cover
PFP-100N/PFP-50N
Note: This dimension applied to PFP-50N.
PFP-M
Y92F-30
Y92A-48B/Y92A-48D
End Plate
Note: Pay attention to the orientation of the adapter when mounting
The protective cover protects the front panel, particularly the
time setting section, against dust, dirt and water drip, as well
as prevents the set value from being altered due to accidental
contact with the time setting knob.
Adapter for Flush Mounting
two or more timers in a vertical or horizontal line.
Y92A-48B
Hard Plastic Cover
(see note)
Y92A-48D
Soft PVC Cover
Note: The Y92A-48B Protective Cover is made of a hard plastic and
PFP-100N2
PFP-S
Note: A total of 12-25 × 4.5 elliptic holes are provided with 6 holes
therefore, must be removed to change the timer set value. However,
since the Y92A-48D Protective Cover is made of PVC, the set value
can be altered by pressing on the surface of the cover.
It may be, however, difficult to make setting changes of the Timer
with the Y92A-48B Protective Cover attached, which must be taken
into consideration before using the Y92A-48B Protective Cover.
When attaching the Y92A-48A to the Timer to be panel-mounted,
use the Y92F-30 Mounting Adapter along with the Timer.
The Protective Cover cannot be, however, used for the H3CA-FA
Series.
cut from each rail end at a pitch of 10 mm between holes.
Twelve, 25 × 4.5 elliptic holes (see note)
H3CA
9