CR4395-EH-120-110-X-CD-ELR-I CR Magnetics Inc, CR4395-EH-120-110-X-CD-ELR-I Datasheet - Page 2

RELAY AC CURRENT SENS 120V 1-10A

CR4395-EH-120-110-X-CD-ELR-I

Manufacturer Part Number
CR4395-EH-120-110-X-CD-ELR-I
Description
RELAY AC CURRENT SENS 120V 1-10A
Manufacturer
CR Magnetics Inc
Series
CR4395r

Specifications of CR4395-EH-120-110-X-CD-ELR-I

Relay Type
Current Sense
Circuit
SPDT (1 Form C)
Contact Rating @ Voltage
10A @ 240VAC
Coil Type
Standard
Coil Voltage
120VAC
Control On Voltage (max)
Adjustable
Control Off Voltage (min)
Adjustable
Mounting Type
Chassis Mount
Termination Style
Quick Connect - .250" (6.3mm)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Coil Current
-
Other names
582-1074

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
CR4395-EH-120-110-X-CD-ELR-I
Manufacturer:
CR Magnetics Inc
Quantity:
135
TRIP STATUS
EH - Energized on High, trips
when sense current is above trip
point and returns to non-trip
status when sense current is
below the trip point.
EL - Energized on Low, trips
when sense current is below trip
point and returns to non-trip
status when sense current is
above the trip point.
LH - Latch on High, trips when
sense current is above trip point
and remains tripped until
supply power is removed.
LL - Latch on Low, trips when
sense current is below trip point
and remains tripped until supply
power is removed.
Shown with Internal Transformer Option (-l)
SUPPLY POWER TERMINALS
1/4" MALE QUICK CONNECT
Another HUNTINGTON ELECTRIC Company
TYPICAL 2 PLACES
2 1/8 (54)
MAX.
7/8 (22.2)
CR4395 -
CRGFS -
3 1/2
(88.9)
.50 (12.7) DIA.
9/32 (7.14)
2 15/16
(74.6)
OUTLINE DRAWING
NC NO COM
1 15/16 (49.2)
1/4" MALE QUICK CONNECT
OUTPUT RELAY TERMINALS
TYPICAL 3 PLACES
100 - 1.65 dia. Window
200 - 1.83 dia. Window
2 1/2 (63.5)
SUPPLY VOLTAGE
All supply voltage tolerances
are ± 10 %
120 - 120 VAC
240 - 240 VAC
24D - 24 VDC
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
TIME-ON DELAY,
TURN CLOCKWISE
AC
DC
TO INCREASE
9/32 (7.14)
3/16 DIA. MOUNTING H
TYPICAL 2 PLACES
INDICATING LED
"ON" WHEN RELAY
IS TRIPPED
-
EXTERNAL CURRENT SENSING TRANSFORMER
The trip ranges shown are for
one wire pass through the
window opening. The trip range
may be proportionally lowered
with additional wire passes
through the window.
PART NUMBER
101 - 10 to 100 AAC
110 - 1.0 to 10 AAC
330 - 3.0 to 30 AAC
660 - 6.0 to 60 AAC
TRIP RANGE
Shown with Remote Current
Transformer Option (-R)
-
-
when the output energizes. The ranges are
greater.
Time-on delay is the time from when the relay trips to
guaranteed minimum, actual range may be slightly
69
NC NO COM
TRIP POINT DIAL
(Specify value of fixed
trippoint with order)
-3.30 trip range shown
-
CD - Calibrated Dial
FP - Fixed Trip Point
- CD
TRIP ON DELAY
A - .5 to 6 Sec.
B - 2 to 25 Sec.
C - .1 - 1 Sec.
X - none
dial provided with
No adjustment
the fixed set
point option
- FP
-
1.65[42.0mm](-100)
1.85[47.0mm(-200)
2.70 [68.6mm](-100)
3.00 [76.2mm](-200)
E-mail: sales@crmagnetics.com
Current Sensing Relay
Electromechanical
Remote Current Transformers
CRGFS - Series
ELR
I - INTERNAL TRANSFORMER
R - REMOTE TRANSFORMER
Relay
NC NO COM
-
OUTPUT OPTIONS
NPN Transistor
Optoisolated
NPN
CR4395 Series
12" [304.8mm](-100 & -200)
Triac, Zero Crossing
0.70 [17.8mm](-100)
1.85 [47.0mm](-200)
Optoisolated
TRC
E

Related parts for CR4395-EH-120-110-X-CD-ELR-I