CR4395-EH-120-110-X-CD-ELR-I CR Magnetics Inc, CR4395-EH-120-110-X-CD-ELR-I Datasheet
CR4395-EH-120-110-X-CD-ELR-I
Manufacturer Part Number
CR4395-EH-120-110-X-CD-ELR-I
Description
RELAY AC CURRENT SENS 120V 1-10A
Manufacturer
CR Magnetics Inc
Series
CR4395r
Datasheet
1.CR4395-EH-120-110-X-CD-ELR-I.pdf
(2 pages)
Specifications of CR4395-EH-120-110-X-CD-ELR-I
Relay Type
Current Sense
Circuit
SPDT (1 Form C)
Contact Rating @ Voltage
10A @ 240VAC
Coil Type
Standard
Coil Voltage
120VAC
Control On Voltage (max)
Adjustable
Control Off Voltage (min)
Adjustable
Mounting Type
Chassis Mount
Termination Style
Quick Connect - .250" (6.3mm)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Coil Current
-
Other names
582-1074
Available stocks
Company
Part Number
Manufacturer
Quantity
Price
Company:
Part Number:
CR4395-EH-120-110-X-CD-ELR-I
Manufacturer:
CR Magnetics Inc
Quantity:
135
E
Current Sensing Relay
Another HUNTINGTON ELECTRIC Company
CR4395 Series
The Relay is available with three different output
configurations, electromechanical relay, op-
toisolated NPN transistor or optoisolated triac.
Specify desired selection in part number.
Arrangement: 1 Form C (SPDT)
Contact Material: Silver-cadmium oxide
Terminals: 3
Mechanical Life: 10 million operations,
Electrical Life: 100,000 operations,
Initial Contact Resistance:
Contact Rating: UL508/873 & CSA
Vce (full off): 30 VDC max.
Isink (full on): 120 mADC max.@ rated full-on
Vce (full on): 1.5 VDC @ 120 mADC Isink
Off state leakage current: 5ua @ 30 VDC
Off state voltage: 240 VAC RMS max.
Minimum switch voltage: 24 VAC RMS
On state current: 0.5 AAC RMS max. continuous
Switching mode: Zero crossing
Off state leakage: 60 ua @ 240 VAC max.
typ.@ rated load
typ. @ rated load
(typical)
50 milliohms max. @ 500 mA, 12 VDC
DC SWITCHING (-NPN)
AC SWITCHING (-TRC)
OUTPUT OPTIONS
1/4”
RELAY (-ELR)
Male QC
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
The CR4395 Series, Current Sensing Relay provides an effec-
tive and highly stable method for monitoring electrical current.
The current-carrying wire is routed through the opening extend-
ing from the top of the case. When current reaches the level set
by the trip point adjustment, the relay trips and starts the ad-
justable timer. After the timer cycles the electromechanical relay
is energized. A precision voltage reference circuit ensures a
highly repeatable trip point.
Applications
Monitor Electrical Heater Elements
Sense Motor Over/Under Loads
Detect Lamp burn-out
Indicate Phase Loss
Features
Variable Trip Point and Time Delay
Monitors Currents from 1 AC to 100 AC Amps
Electrical Isolation Between Circuits
Output Relay Rated up to 20 Amps
LED Trip Status Indicator
Dead Band Prevents Relay Chatter
Calibrated Dial Option Available
External Current Transformers Available
Specifications
Mounting:
Environmental:
Power-On Delay: 100 MS MAX
Hysteresis: 5% Max.
Input Supply Power:
Sensed Current:
Weight 0.5 LBS.
Regulatory Agencies
3/16” dia. clearance holes on 1
Operating Temperature: -30° C to +60° C
Storage Temperature: -55° C to +85° C
Terminals: 2
Max. Continuous: 200% Full Scale
Frequency: 60-400 Hz *
VOLTAGE
240 VAC
240 VAC
125 VAC
28 VDC
*All specifications for operation at 60 Hz only
68
1/4
” Male QC
LOAD TYPE
Resistive
Resistive
Motor
Motor
E-mail: sales@crmagnetics.com
N.O. CONTACT
15/16
20A
2HP
1HP
20A
” by 2
15/16
”centers
N.C. CONTACT
1/2 HP
1/4 HP
10A
10A
Related parts for CR4395-EH-120-110-X-CD-ELR-I
CR4395-EH-120-110-X-CD-ELR-I Summary of contents
Page 1
... CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119 Web: http://www.crmagnetics.com Another HUNTINGTON ELECTRIC Company The CR4395 Series, Current Sensing Relay provides an effec- tive and highly stable method for monitoring electrical current. The current-carrying wire is routed through the opening extend- ing from the top of the case ...
Page 2
... The ranges are guaranteed minimum, actual range may be slightly greater. EXTERNAL CURRENT SENSING TRANSFORMER 69 Current Sensing Relay CR4395 Series 2.70 [68.6mm](-100) 3.00 [76.2mm](-200) 12" [304.8mm](-100 & -200) 1.65[42.0mm](-100) 1.85[47.0mm(-200) Remote Current Transformers ...