TLR5-S S ERIES POWER SYSTEM
2.3.1 DC circuit 1
(-)
Bulk Output
(+)
Figure 4 - DC Wiring Diagram (Circuit #1)
Each system is equipped with two double hole lug DC connection pads located behind the rear
panel as shown in Figure 10. Select a wire size for each position according to the maximum load
current as shown in Table 9. If the rack is to receive additional power modules at a later date,
select wiring for the maximum future installation. This rack is not designed for connection to a
battery system without the use of an external distribution panel. The polarity of the system is uni-
versal, therefore the polarity of the output is determined by the system grounding.
2.3.2 DC cable sizing
Size DC cable for the total capacity of the power modules installed. For example, a rack contain-
ing four TL150024 (24V, 60A) power modules has a total capacity of 240 A. Using the tables
below this system will require a 4/0 AWG cable or two 2 AWG cables per output.
Page. 14
Revision A3 : July 2005