S82Y-L15A Omron, S82Y-L15A Datasheet - Page 4

no-image

S82Y-L15A

Manufacturer Part Number
S82Y-L15A
Description
KIT PARALLEL CABLE FOR S82L
Manufacturer
Omron
Series
S82Lr
Datasheets

Specifications of S82Y-L15A

Accessory Type
Connection Kit
For Use With/related Products
S82L 150W Power Supplies
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S82YL15A
S82L
Engineering Data
The protective function prevents damage to the load as well as the
Power Supply itself due to overload. If the load current rises above
the overload set value (105% of the rated load current), the protec-
tive function will engage and the voltage will be reduced. Reset is
automatic, so the Power Supply will return to normal operation when
the overload condition is corrected.
If an overload condition continues for more than 5 s, the output will
be shut off. In this situation, reset is not automatic. The input power
must be turned off for at least 30 s, and then turned on again to reset
the Power Supply.
4
Derating Curve
Overload Protection
Inrush Current, Rise Time, Hold Time
Note: The derating curve differs depending on the mount-
ing direction of the Power Supply. The curve above
was obtained with the Power Supply mounted in the
standard position.
Ambient Temperature ( C)
AC input voltage
AC input current
Output voltage
Standard installation
Natural air
cooling
Forced air
cooling
Input ON
Inrush current on input application
Rise time
(300 ms max.)
The protective function prevents damage to the load as well as the
Power Supply itself due to overvoltage. The output is shut off if the
output voltage rises above about 120% of the rated voltage. The in-
put power must be turned off for at least 30 s, and then turned on
again to reset the Power Supply.
90%
Overvoltage Protection
Rated output
voltage
Approx.
20%
10%
–10%
Output shut off after 5 s
Input OFF
Output current (%)
Hold time
(20 ms min.)
Variable
98%
Rated voltage
Overvoltage
S82L