S82Y-L15A Omron, S82Y-L15A Datasheet - Page 12

no-image

S82Y-L15A

Manufacturer Part Number
S82Y-L15A
Description
KIT PARALLEL CABLE FOR S82L
Manufacturer
Omron
Series
S82Lr
Datasheets

Specifications of S82Y-L15A

Accessory Type
Connection Kit
For Use With/related Products
S82L 150W Power Supplies
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S82YL15A
Cat. No. T07-E1-2
OMRON Corporation
Systems Components Division
28th Fl., Crystal Tower Bldg.
1-2-27, Shiromi, Chuo-ku,
Osaka 540 Japan
Phone: 06-949-6012 Fax: 06-949-6021
S82L
To ensure that the voltage drop is the same between each Power
Supply and load, the length and cross sectional area of the wires
used should be uniform, and the system should be wired as in figure
below.
Do not wire the Power Supplies as shown below. It will cause output
voltage imbalance, so that one of the units will supply exceeding
current, causing the overload protection to engage, resulting in an
unstable current and reducing product life expectancy.
Attaching Mounting Brackets
30/60/100 W
Insert the hook on the corner of the bracket into the hole provided in
the Power Supply housing. First, attach the bracket to the unit with
one screw and then install the unit.
150 W
Insert the hook on the corner of the bracket into the hole provided in
the Power Supply housing. Screw in both screws for each bracket
and install the unit.
12
CB –S
Shielded wire
CB –S
+V
–V
Shielded wire
+V
–V
Mounting Brackets
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
(–) (+)
Load
CB –S
In the interest of product improvement, specifications are subject to change without notice.
+V
–V
CB –S
Power Supply housing
Hook
CB –S
+V
–V
Holes
Shielded wire
+V
–V
(–)
Load
CB –S
Load
(+)
(–)
(+)
+V
–V
Adjusting the Output Voltage
Follow the procedure below when adjusting the output voltage of a
master/slave system.
1. Connect the two Power Supplies in parallel and decide which
2. Turn the voltage adjuster (V. ADJ) of the slave unit all the way
3. Adjust the voltage adjuster (V. ADJ) of the master unit to the
4. Slowly turn the voltage adjuster (V. ADJ) of the slave unit
NOTICE
1. It is recommended to set equal output voltages to both
2. Even if one Power Supply fails to operate, both output
3. 30, 60, and 100 W type Power Supplies cannot perform
4. Be sure to use shielded wires when connecting CB and
unit will be the master.
clockwise.
desired voltage.
counterclockwise and set value just before output voltage
drop.
Power Supplies for safety reasons. If the master Power
Supply stops operation by input failure or breakage, the
set output value of the slave Power Supply will be
output.
LED indicators may be lit if the other Power Supply is in
operation.
parallel operation as they are not provided with Current
Balance Function.
-S terminals to prevent noise interference with
operation.
Printed in Japan
0897-0.5C