S82Y-VS30P Omron, S82Y-VS30P Datasheet - Page 22

no-image

S82Y-VS30P

Manufacturer Part Number
S82Y-VS30P
Description
MOUNTNG BRKT SIDE FOR S8VM 15/30
Manufacturer
Omron
Series
S8VSr
Datasheets

Specifications of S82Y-VS30P

Accessory Type
Mounting Bracket(s)
For Use With/related Products
S8VS 15W & 30W Power Supplies
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S82YVS30P
Maintenance Forecast Monitor Function
The Power Supply is equipped with electrolytic capacitors.
The electrolyte inside the electrolytic capacitor penetrates the sealing
rubber and evaporates as time passes since it is manufactured, which
causes deterioration of characteristics such as decreasing the
capacitance, etc.
Due to this deterioration of the characteristics of the electrolytic
capacitor, the Power Supply decreases its performance as time
passes.
Relationship between Indicated Values and Output of Set Values
Principle of Operation
The deterioration speed of the electrolytic capacitor varies
considerably according to the ambient temperature. (Generally the
speed follows “Rule of Two for every 10°C”; for every 10°C increase
in temperature the rate of degradation doubles according to
Arrhenius’s equation.) The S8VS-@@@24A@@ monitors the
temperature inside the power supply, and calculates the amount of
deterioration according to the running hours and inside temperature.
Judging by this amount of deterioration, the power supply will give the
alarm indication and output when the period left for maintenance
reaches the set value.
Note: 1. Due to degradation of internal electronic parts, replace the
Initial capacity
Capacity level
at replacement
Note: This function can be set only on the S8VS-09024A@@, S8VS-12024A@, S8VS-18024A@, S8VS-24024A@, and S8VS-48024A.
2. The maintenance forecast is accelerated or decelerated
3. Acceleration or deceleration of the maintenance forecast
4. The accuracy of the maintenance forecast function may be
power supply approximately 15 years after purchase even if
indication and output of maintenance forecast monitor are
not issued.
according to operating conditions. Periodically check
indication.
may cause the output to repeatedly go ON/OFF.
Only the S8VS-09024A@@, S8VS-12024A@, S8VS-
18024A@, S8VS-24024A@, and S8VS-48024A are
equipped with output.
adversely affected by applications in which the AC input is
frequently turned ON/OFF.
Capacity of Capacitor
Maintenance forecast monitor output
L: Maintenance forecast set value (See note.)
0.0 to 5.0, 0.5 steps
Main display
(L−0.5)
L=2.5
L=0.5
5.0
In case of setting L between 2.5 and 5.
The maintenance forecast monitor function shows an approximate
period left for maintenance of the Power Supply due to deterioration
of electrolytic capacitors. When the period left for maintenance that
the power supply forecasts reaches the set value, an alarm is
indicated and an output signal is triggered.
Use this function to know the approximate replacement timing of the
Power Supply.
Note: The maintenance forecast monitor function indicates an
Reference Values (15-W to 480-W Models)
Note: The maintenance forecast is the service life (the power
Reliability
(MTBF)
Life
expectancy
Item
The numerical value
decreases with time.
approximate period left for maintenance, based on
deterioration of the electrolytic capacitor. It does not predict
failures caused by other reasons.
supply’s internal temperature is monitored at all times) of the
internal electrolytic capacitor in actual operating conditions,
and varies according to the customer’s operating conditions.
15 years is taken as the maximum period of the maintenance
forecast.
15 W to 240 W:
135,000 hr min.
480 W:
60,000 hr min.
10 yr min.
2.5
Value
2.0
1.5
"1.0" is displayed on the main display for the
duration that the maintenance forecast up to
replacement satisfies the condition 1.0 ≤ T < 1.5.
MTBF stands for Mean Time
Between Failures, which is
calculated according to the
probability of accidental device
failures, and indicates reliability of
devices.
Therefore, it does not necessarily
represent the life of the Product.
The life expectancy indicates
average operating hours under the
ambient temperature of 40°C and a
load rate of 50%. Normally this is
determined by the life expectancy of
the built-in aluminum electrolytic
capacitor.
1.0
0.5
Definition
T: Maintenance time
until replacement
0
S8VS
22

Related parts for S82Y-VS30P