S8TS-06024-E1. Omron, S8TS-06024-E1. Datasheet - Page 3

no-image

S8TS-06024-E1.

Manufacturer Part Number
S8TS-06024-E1.
Description
BLOCK BASIC 24V 2.5A SCREW TERM
Manufacturer
Omron
Series
S8TSr
Datasheets

Specifications of S8TS-06024-E1.

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
60W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 2.5A
Size / Dimension
4.72" L x 1.69" W x 4.72" H (120mm x 43mm x 120mm)
Power (watts) - Rated
60W
Operating Temperature
-10°C ~ 50°C
Efficiency
75%
Approvals
CE, cUL, cUR, UL, VDE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8TS06024E1
5-V Models (Basic Block: S8TS-02505@)
Note: 1. The output current specification is defined at the power supply output terminals.
■ Reference Value
Efficiency (typical)
Input
Output
(See note
1.)
Additional
functions
Other
Reliability (MTBF)
Life expectancy
2. Refer to the Engineering Data Section for details.
Item
Voltage
Frequency
Current
Power factor
Leakage current
Inrush current
(25°C, cold start)
(See note 2.)
Voltage adjustment range
Ripple
Input variation influence
Temperature variation influence
Load variation influence
Startup time (See note 2.)
Hold time (See note 2.)
Overcurrent protection (See note 2.)
Overvoltage protection (See note 2.)
Parallel operation
N+1 redundant system
Series operation
Undervoltage indicator (See note 2.)
Undervoltage detection output
(See note 2.)
Ambient operating temperature
(See note 2.)
Ambient humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
Electromagnetic interference
EMI
Power factor correction
EMS
Approved standards
Weight
250,000 hrs min.
10 yrs min.
Item
Value
100 V input
200 V input
100 V input
240 V input
100 V input
200 V input
MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental
device failures, and indicates reliability of devices. Therefore, it does not necessarily represent the life of the
product.
The life expectancy indicates average operating hours under the ambient temperature of 40° C and a load rate
of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.
62% min. (with rated input, 100% load)
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 63 Hz)
0.7 A max.
0.4 A max.
0.8 min. (with rated input, 100% load)
0.35 mA max.
0.7 mA max.
25 A max.
50 A max.
5 V ± 10% (with V. ADJ) (See note 1.)
2% (p-p) max.
0.5% max. (with 85 to 264 VAC input, 100% load)
0.05%/° C max. (with rated input and output)
1.5% max. (with rated input, 10% to 100% load)
1,000 ms max.
20 ms min. (with 100/200 VAC, rated input)
105% to 125% of rated load current, inverted L drop type, automatic reset
Yes
No
No
Yes (with the external diode)
Yes (color: red)
Yes (open collector output), 30 VDC max., 50 mA max.
Operating: Refer to the derating curve in Engineering Data.
Storage: − 25 to 65°C (with no icing or condensation)
Operating: 25% to 85%, Storage: 25% to 90%
3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection current: 20 mA)
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and GR terminal; detection current: 20 mA)
1.0 kVAC for 1 minute (between all outputs and GR terminal; detection current: 20 mA)
100 MΩ min. (between all outputs and all inputs, and between all outputs and GR terminal) at
500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s
Yes (color: green)
Conforms to FCC Class A, EN50081-1
Conforms to EN50081-1/1992
Conforms to EN61000-3-2, EN61000-3-2A14
Conforms to EN61000-6-2/1999
UL: 508 (Listing), 1950, 1604 (Class I, Division 2, Groups A, B, C, D Hazardous Locations)
cUL: CSA C22.2 No.14, No.213 (Class I, Division 2, Groups A, B, C, D
EN/VDE: EN50178 (=VDE0160), 60950 (=VDE0806)
450 g max.
Hazardous Locations), No. 950
2
, 3 times each in ±X, ±Y, and ±Z directions
Definition
Switching Power Supply
Single operation
S8TS
3

Related parts for S8TS-06024-E1.