K2CM-1L Omron, K2CM-1L Datasheet - Page 3

no-image

K2CM-1L

Manufacturer Part Number
K2CM-1L
Description
RELAY MOTOR PROTECTIVE 8-26A
Manufacturer
Omron
Series
K2CMr
Datasheet

Specifications of K2CM-1L

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
K2CM1L
■ Characteristics
Note: This means that no malfunction occurs with the open-phase element, but the operating value of the overload element may vary.
Variation due to
temperature
fluctuation
Variation due to
voltage fluctuation
Variation due to
frequency
fluctuation
Insulation resistance
Dielectric strength
Permissible impulse voltage
Overcurrent strength of main circuit
Overvoltage strength of control power
supply circuit
Variation due to waveform distortion
Vibration
Shock
Test current
(reference only)
Service life
Ambient temperature
Humidity
Altitude
At 20 ±20 °C
At 20 ±30 °C
At 85% to 110% of
rated voltage
At 95% to 105% of
rated frequency
Operating time
Setting
characteristics of
operating time
Overcurrent:
Open-phase:
Reverse-phase: ±10% of operating value, ±10% of operating time
Overcurrent:
Open-phase:
Reverse-phase: ±20% of operating value, ±20% of operating time
Overcurrent:
Open-phase:
Reverse-phase: ±5% of operating value, ±10% of operating time
10 MΩ min. (between current-carrying terminals and mounting panel)
5 MΩ min. (between current-carrying terminals and between contact poles)
2,500 VAC (between current-carrying terminals and mounting panel and between current-carrying
terminals)
1,000 VAC (between contact poles)
Current reverse-phase detection models:
Voltage reverse-phase detection models:
No abnormality develops when 20 times the set current value is applied for 2 s, 2 times with a 1-
minute interval.
No abnormality develops when 1.15 times the relay’s rated voltage is applied once for 3 hours.
No malfunction occurs when pulse containing 100% of the 2nd to 9th harmonics is applied (open-
phase switch set to “Low”). (See note.)
Malfunction: 10 to 55 Hz, 0.3-mm double amplitude (in X, Y, and Z directions for 10 minutes each)
Destruction: 10 to 25 Hz, 2-mm double amplitude (in X, Y, and Z directions for 2 hours each)
Malfunction: 98 m/s
Destruction: 294 m/s
Set time value
Approx. ±30% of the maximum setting value
Electrical: 10,000 operations
Operating: −10 to 60 °C (with no icing)
Storage:
35% to 85%
2,000 m max.
6,000 V (between current-carrying terminals and mounting panel)
4,500 V (between current-carrying terminals and between control power supply terminals)
Waveform: 1.2/50 µs
4,500 V (between current-carrying terminals and mounting panel)
Waveform: 1.2/50 µs
−25 to 65 °C
±5% of operating value, ±10% of operating time
±10% of operating value, ±10% of operating time
±10% of operating value, ±20% of operating time
±20% of operating value, ±20% of operating time
±5% of operating value, ±10% of operating time
±5% of operating value, ±10% of operating time
2
2
(approx. 10 G) in X, Y, and Z directions
(approx. 30 G) in X, Y, and Z directions
K2CM
3

Related parts for K2CM-1L