K2CM-1L Omron, K2CM-1L Datasheet - Page 14

no-image

K2CM-1L

Manufacturer Part Number
K2CM-1L
Description
RELAY MOTOR PROTECTIVE 8-26A
Manufacturer
Omron
Series
K2CMr
Datasheet

Specifications of K2CM-1L

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
K2CM1L
Safety Precautions
■ Correct Use
• The operation check using the test button is intended to check the
• The operating time of inverse-type models and the lock time of the
• The reverse-phase can be detected in the wiring up to the current
• Current reverse-phase detection models cannot be used in applica-
• Jogging of the motor can be performed. For details, consult your
• When using the K2CM to control inching shorter than 0.5 s, the
• The K2CM is basically intended to protect three-phase loads. Its
• When applying the K2CM to a circuit with a high imbalance factor
• When applying the K2CM to the protection of three-phase trans-
1
2
3
4
5
6
7
Combination
operation of the overcurrent functions. Therefore, be sure to turn
ON the overcurrent switch. Also, at this time, turn OFF the open-
phase switch and reverse-phase switch to prevent unnecessary
operations from being performed.
instantaneous-type models depend upon the set operating time.
Therefore, do not hold down the test button for more than the set
operating time.
transformer (including an external current transformer). Check the
wiring between the current transformer and the motor before start-
ing the motor.
tions that do not allow even momentary reversals of motor direc-
tion.
OMRON representative.
reverse-phase level detection circuit may operate. In this case, be
sure to use the K2CM with the reverse-phase switch set to OFF.
overcurrent function, however, can also be applied to single-phase
loads. In this case, the conductors can be passed through the holes
in any direction and sequence.
due to the nature of the power supply or load, actually measure the
imbalance factor and select the open-phase sensitivity accordingly
(i.e., set the open-phase switch to either the high or low position).
The K2CM cannot be used if the imbalance factor is 60% or higher.
formers, give consideration to the imbalance factor due to single-
phase loads.
ON
ON
ON
ON
Overcur-
Function setting switches
rent
ON
ON
ON
ON
Open-
phase
ON
ON
ON
ON
Reverse-
phase
ON
OFF
OFF
OFF
Overcur-
rent
LED indicators
ON
ON
OFF
OFF
Open-
phase
ON
ON
ON
ON
Reverse-
• A power supply with a frequency other than commercial frequency
• Use of circuits containing a high percentage of harmonics, such as
• When applying the K2CM to the protection of a high-voltage motor
• Never tamper with the trip indicator. Use the reset switch to reset
• When a power failure occurs in the control power supply, the K2CM
• Be sure to remount the front cover after detaching it for operating or
• The rectifier and control circuits are combined by tightening the two
• The variable resistors used to make settings are equipped with
• When using the K2CM-@@@A (instantaneous, automatic reset-
• Be sure to provide the control power supply for the K2CM-@@@@V
• If current reverse-phase detection models are used in a circuit with
phase
cannot be used as the control power supply.
circuits incorporating SCR control circuits, VVVF inverters, or recti-
fiers, may cause errors and malfunctions. Consult your OMRON
representative for details.
or low-voltage, high-capacity motor, use an external rectifier that
does not saturate at currents up to 600% of the rated motor current
and thus permits a large overcurrent; otherwise, the K2CM will out-
put a tripping signal because of imbalanced operation when an
overcurrent occurs and, with reverse-type models, the motor may
be damaged by burning.
the K2CM.
is not reset even when the reset switch is pressed. This is not an
error. The K2CM can be reset only when control power is applied to
it.
setting the switches on the front panel.
screws on the right and left sides. Never loosen these screws.
mechanisms to stop them rotating outside the valid scale range. Do
not rotate the variable resistors at a torque of 1 kg·cm or more.
ting), be sure to apply power to the Motor Protective Relay from the
same power line as the magnet contactor for switching the motor.
(voltage reverse-phase detection) from the same line as the motor.
distorted current waveforms, the reverse-phase element may per-
form an unwanted operation. In such circuits, use of the K2CM-
@@@@V (voltage reverse-phase detection) is recommended
because it is not affected at all by current waveform distortion.
If the inputs for combinations of two or more functions are
simultaneously generated, the K2CM detects the inputs in
the order reverse-phase, open-phase, overcurrent. Take
combination 4 as an example. If the open-phase and over-
current occur at the same time, there is insufficient time to
detect the overcurrent because the open-phase is first de-
tected and the K2CM outputs the tripping signal (causing
the magnet contactor to turn off). Therefore, the overcur-
rent indicator does not light.
NOTE
K2CM
14