ing time
Q
Operat-
setting
What is the range of the operating time for inverse
operation?
Use the values in the following table as guidelines.
11.7 to 29.1 6.0 to 8.0
13.7 to 32.8 7.0 to 9.0
15.7 to 36.4 8.0 to 10.0
17.6 to 40.0 9.0 to 11.0
Percentage of current
1.0 to 7.3
1.9 to 10.9 1.0 to 3.0
3.9 to 14.6 2.0 to 4.0
5.9 to 18.2 3.0 to 5.0
7.8 to 21.9 4.0 to 6.0
9.8 to 25.5 5.0 to 7.0
200%
setting
0.5 to 2.0
600%
(s)
Time scale: × 4
1
2
3
4
5
6
7
8
9
10
ing time
Operat-
setting
15.7 to 58.3
23.5 to 72.8 12.0 to 20.0
31.3 to 87.4 16.0 to 24.0
39.2 to 102
47.0 to 117
54.9 to 131
62.7 to 146
70.5 to 160
3.9 to 29.1
7.8 to 43.7
Percentage of current
200%
setting
20.0 to 28.0
24.0 to 32.0
28.0 to 36.0
32.0 to 40.0
36.0 to 44.0
2.0 to 8.0
4.0 to 12.0
8.0 to 16.0
600%
(s)
SET-3A
SET-3B
Note: 1. This is the output voltage when connected to an SE Motor Protective
SET-3A/3B Current Converter
Three-phase Input Current and Output
Voltage Characteristics
Reference
Output voltage
DC output voltage (VDC) 8.4
Q
Q
Q
Three-phase current Percentage of SET-3@ current setting tap value
20
40
80
2. When testing an SE or SAO with the output voltages shown in the
What is the approximate DC output voltage of an SET-3@
Current Converter?
Use the voltages in the following chart as a guide.
Can the SE be used for single-phase applications?
Yes it can, but the open-phase element cannot be used. Turn
OFF the open-phase setting on the function setting DIP
switch. Refer to the Q&A section on the SAO Current Sensor
for the overcurrent setting method. Consider using an SAO-
@S Current Sensor (for single-phase).
What will happen if a control power supply with an
automatic reset is taken from the same circuit as the
motor circuit?
The allowable fluctuation range for a control power supply
with an automatic reset is 85% to 110%. An open phase in
the motor circuit power supply will reduce the voltage to up to
50%. Thus, a power supply with an automatic reset will not
be able to operate.
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Relay or SAO Current Sensor. When connected to any other model,
the output voltages will be about the same as those shown in the
above table when the input impedance is 13.3 kΩ.
above table, consider the voltage values to be a guideline only.
0
0
0
0
SET-3@
Note: This shows the characteristics
16
2
4
8
at the “10” mark of the SE
current scale.
16
32
4
8
Three-
phases
12
24
48
6
16
32
64
8
40
DV
10
20
40
80
Current setting range
Digital
voltmeter
7 8
21
12
24
48
96
SE
100
112
14
28
56
128
16
32
64
42
200
144
18
36
72
160
20
40
80
84
Three-phase current (A)
176
400
22
44
88
192
24
48
96
123
104
208
26
52
SE
600
112
224
28
56
13