MSR33RT ALLEN-BRADLEY [Allen-Bradley], MSR33RT Datasheet

no-image

MSR33RT

Manufacturer Part Number
MSR33RT
Description
Monitoring Safety Relays
Manufacturer
ALLEN-BRADLEY [Allen-Bradley]
Datasheet
Safety Relays
Monitoring Safety Relays
Minotaur MSR33RT/RTP
Description
The Minotaur MSR33RT/RTP is a microprocessor-based,
monitoring safety relay, with safety-rated, solid state outputs.
The MSR33RT/RTP is designed to operate with dual channel inputs
where one channel is normally closed and the other is normally
open. The Sipha sensors can be connected to the MSR33RT/RTP
inputs.
Test pulses are used to dynamically check the input circuits. All
inputs and outputs are short-circuit protected.
The reset capability of the MSR33RT/RTP allows it to set up for
monitored manual or automatic reset. A start-up test can be enabled
if automatic reset is used. The start-up test requires the inputs to be
cycled before energizing the outputs. The reset and start-up test is
determined by the connection wiring.
The outputs include two normally-open safety rated outputs that can
be connected to loads up to 2A at 24V DC. These outputs can be
used to send a safety stop signal to a machine or manufacturing
system.
The MSR30 also has one solid state, normally-open auxiliary output,
which must only be used to indicate status of the MSR33RT/RTP.
Features
• Category 4 per EN954-1
• Stop Category 0
• 2 Solid State N.O. Safety Outputs
• 1 Solid State N.O. Auxiliary Output
• 1 N.O. & 1 N.C. Input
4-28
Housing with removable
terminals shown.
Specifications
Wiring Terminations
Standards
Safety Category
Approvals
Power Supply
Power Consumption
Safety Inputs
Max. Allowable Input Resistance
Outputs
Output Rating Safety
Short-Circuit Protection
Power On Delay
Response Time
Recovery Time
Indication LEDs
Pwr LED 3s Blink
Operating Temperature
Humidity
Enclosure Protection
Terminal Protection
Pollution Degree
Conductor Size
Mounting
Weight
Vibration
Shock
Auxiliary
2 Blinks
4 Blinks
Continuous Blinking
See Output Ratings on page 1-29 for details. Consult factory for ratings not
Diagnostics Constant
shown.
S11 & S21 Pulse checking dynamic output
S12 & S22 Input contacts
S11 – S34 Automatic reset, start-up test disabled
S21 – S34 Automatic reset, start-up test enabled
A1 – S34 Reset switch
A1 – Y2 Monitoring circuit
EN954-1, ISO13849-1, IEC/
EN60204-1, ANSI B11.19,
AS4024.1
Cat. 4 per EN954-1 (ISO13849-1)
CE for all applicable directives, C-
Tick, cULus, TUV
24V DC SELV (max with no load)
electrically separate supply source
3W
1 N.C. & 1 N.O.
200 ohms
2 N. O. Safety, Solid State
1 N.O. Aux, Solid State
2A @ 24VDC
50mA @ 24VDC
Inputs and outputs (safety and aux)
3s
15ms
20ms
Green = Power (Pwr)
Green = CH1 Energized
Green = CH2 Energized
Initialization
Normal operation
Config. change during operation
Solid state output switch fault
Internal Fault
-5°C to +55°C (+14° to +131°F)
90% RH
IP40 (NEMA 1), DIN VDE 0470-1
IP20
2
0.2 – 2,5mm
In panel enclosure (IP54)
35mm DIN rail
130g (0.287 lbs)
10-55Hz, 0.35mm
10g, 16ms, 100 shocks
2
(24 – 14AWG)

Related parts for MSR33RT

MSR33RT Summary of contents

Page 1

... Test pulses are used to dynamically check the input circuits. All inputs and outputs are short-circuit protected. The reset capability of the MSR33RT/RTP allows it to set up for monitored manual or automatic reset. A start-up test can be enabled if automatic reset is used. The start-up test requires the inputs to be cycled before energizing the outputs ...