MSR10D ALLEN-BRADLEY [Allen-Bradley], MSR10D Datasheet

no-image

MSR10D

Manufacturer Part Number
MSR10D
Description
Monitoring Safety Relays with Delayed Outputs
Manufacturer
ALLEN-BRADLEY [Allen-Bradley]
Datasheet
Safety Relays
Monitoring Safety Relays with Delayed Outputs
Minotaur MSR10D
Description
The MSR10RD has 2 N.C. dual channel input for use with gate
interlocks and emergency stop buttons in higher risk applications.
The MSR10RD has output monitoring that accommodates
automatic/manual or monitored manual reset. Automatic/manual
reset can use a jumper or can be used to check operation of the
contacts. Monitored manual requires the use of a manually operated
normally open momentary switch to activate the outputs.
The MSR10RD has 8 N.O. instantaneous safety outputs and 1 N.C.
instantaneous auxiliary outputs as well as 1 N.O. safety and 1 N.C.
auxiliary delayed outputs. The delay is set by an internal potentiometer.
The safety outputs have independent and redundant internal
contacts to help ensure the safety function. The auxiliary contact is
an nonsafety output intended to provide an external signal about the
status of the safety outputs.
Features
• Category 3 per EN 954-1
• Stop category 0 and 1
• 2 N.C. dual channel input
• 8 N.O. instantaneous safety outputs
• 1 N.C. instantaneous auxiliary output
• 1 N.O. delayed safety output
• 1 N.C. delayed auxiliary output
• Automatic/manual or monitored manual reset
• 152mm wide housing
4-42
Specifications
Standards
Category
Approvals
Power Supply
Power Consumption
Safety Inputs
Input Simultaneity
Maximum Input Resistance
Reset
Outputs
60947-5-1 (Inductive)
Thermal Current (non switching) 4A
Fuses Input (internal, replace.)
Min. Switched Current/Voltage
Maximum Dropout Time
Indication LEDs
Impulse Withstand Voltage
Installation Group
Pollution Degree
Operating Temperature
Humidity
Enclosure Protection
Terminal Protection
Conductor Size
Torque Settings—term. screws
Case Material
Mounting
Weight
Electrical Life
Mechanical Life
Vibration
Shock
See Output Ratings on page 1-29 for details. Consult factory for ratings not
220V AC/1.7A/375VA cos =0.6
Output (external)
220V AC/4A/880VA cos =0.35
shown.
Output Utilization per IEC
10V DC/0.01A/0.1W
30V DC/2A/60W
EN 954-1, ISO 13849-1, IEC/EN
60204-1, IEC 60947-4-1, IEC
60947-5-1, ANSI B11.19, AS4024.1
Cat. 3 per EN 954-1 (ISO 13849-1)
C-Tick, CE marked for all
applicable directives and cULus
24V AC/DC and 110/230V AC
<4VA
2 N.C.
0.5s
500
Monitored Manual or Auto./Manual
8 N.O. Safety Instantaneous
1 N.O. Safety delayed 0.1 to 10s
1 N.C. Auxiliary Instantaneous
1 N.C. Auxiliary delayed 0.1 to 10s
B300, AC-15
P300, DC-13
500mA time lag
5A quick acting
10mA/10V
50ms instantaneous
Red = Power On
Green = K1 Closed
Green = K2 Closed
Green = Off Delay Closed
2500V
C in accordance with VDE 0110
3
-10°C to +55°C (+14°F to +131°F)
90% RH
IP40, (NEMA 1), DIN 0470
IP20, DIN 0470
1 x 2.5mm
1 x 4mm
1N m (8.85lb in)
Red Polycarbonate
35mm DIN rail
1054g (2.32lbs)
100,000 operations
500,000 operations
1,000,000 operations
2,000,000 operations
2,000,000 operations
0.75mm (0.30in) peak, 10-55Hz
30g, 11ms half sine
4A/250V AC, 4A/125V AC
3A/24V DC
2
2
(12AWG) solid
(14AWG) stranded,

Related parts for MSR10D

MSR10D Summary of contents

Page 1

... Safety Relays Monitoring Safety Relays with Delayed Outputs Minotaur MSR10D Description The MSR10RD has 2 N.C. dual channel input for use with gate interlocks and emergency stop buttons in higher risk applications. The MSR10RD has output monitoring that accommodates automatic/manual or monitored manual reset. Automatic/manual reset can use a jumper or can be used to check operation of the contacts ...

Page 2

... S13 S14 MSR10RD Stop - S23 S24 Safety Relays Minotaur MSR10D Delayed Timing Catalogue Number 440R-G23029 0.1 to 10s 1 second fixed delay 440R-G23067 0.5 second fixed delay 440R-G23068 Catalogue Number 440R-A31562 S13 S14 ...

Related keywords