MSR230P ALLEN-BRADLEY [Allen-Bradley], MSR230P Datasheet

no-image

MSR230P

Manufacturer Part Number
MSR230P
Description
Modular Monitoring Safety Relays
Manufacturer
ALLEN-BRADLEY [Allen-Bradley]
Datasheet
Safety Relays
Modular Monitoring Safety Relays
Minotaur MSR230P
Description
The MSR230P is an output expansion module for the modular
Minotaur MSR200 family of monitoring safety relays. It can be
connected to either the MSR210P or MSR211P base unit to provide
additional outputs.
Up to 2 MSR230P output modules can be connected to one base
unit by simply removing the terminator, included with each base
unit, and connecting the ribbon cables of the neighboring module.
The connecting ribbon cable provides power to the MSR230P as
well as a check on its status. The terminators must be inserted into
the final output module.
The MSR230P has four safety rated outputs that work in parallel
with the safety outputs of the base unit. When the output of the base
unit is activated, the outputs of the MSR230P are also activated.
The outputs are 4 normally open safety rated outputs. The safety
outputs have independent and redundant internal contacts to help
ensure the safety function.
Features
• 4 N.O. safety outputs
• 2 Diagnostic LEDs
• Removable terminals
4-80
Specifications
Standards
Approvals
Category
Power Supply
Power Consumption
Fuses Output (external)
Outputs
Output Utilization per
IEC60947-4-1 (Resistive)
60947-5-1 (Inductive)
Thermal Current (non switching) 1x6A, 2x4A
Output, Solid State
Min. Switched Current/Voltage
Contact Material
Response Time
Indication LEDs
Impulse Withstand Voltage
Pollution Degree
Operating Temperature
Humidity
Enclosure Protection
Terminal Protection
Conductor Size
Torque Settings—term. screws
Case Material
Mounting
Weight
Electrical Life
Mechanical Life
Vibration
Shock
See Output Ratings on page 1-29 for details. Consult factory for ratings not
220V AC/1.7A/375VA cos =0.6
222V AC/4A/880VA cos =0.35
shown.
Output Utilization per IEC
10V DC/0.01A/0.1W
30V DC/2A/60W
EN 954-1, ISO 13849-1, IEC/EN
60204-1, IEC 60947-4-1, IEC
60947-5-1, ANSI B11.19, AS4024.1
C-Tick, CE marked for all
applicable directives, cULus, & TÜV
Cat. 4 per EN954-1 (ISO13849-1)
24V DC from the base unit
1.5W
6A Slow Blow or 10A Quick Blow
4 N.O. Safety
AC-1: 6A/250V AC
DC-1: 6A/24V DC
B300, AC-15
P300, DC-13
20mA @ 30V DC
10ma/10V DC
AgSnO
Does not add additional response
time to base module
Green = CH1 Output Active
Green = CH2 Output Active
2500V
2
-5°C to +55°C (+23°F to 131°F)
90% RH
IP40 (NEMA 1)
IP20
0.2–4mm
0.4–0.5 Nm (3.54–4.43lb•in)
Polyamide PA 6.6
35mm DIN rail
215g (0.47lbs)
100,000 operations
500,000 operations
1,000,000 operations
2,000,000 operations
2,000,000 cycles
10-55 Hz, 0.35mm
10g, 16ms, 100 shocks
3A/250V AC, 3A/125VAC
2.5A/24V DC
2
+ 2 Au
2
(24–12 AWG)

Related parts for MSR230P

MSR230P Summary of contents

Page 1

... Minotaur MSR200 family of monitoring safety relays. It can be connected to either the MSR210P or MSR211P base unit to provide additional outputs MSR230P output modules can be connected to one base unit by simply removing the terminator, included with each base unit, and connecting the ribbon cables of the neighboring module. ...