H7CX OMRON [Omron Electronics LLC], H7CX Datasheet - Page 5

no-image

H7CX

Manufacturer Part Number
H7CX
Description
Multifunction Preset Counter
Manufacturer
OMRON [Omron Electronics LLC]
Datasheet

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
H7CX-A-N AC100-240
Manufacturer:
Omron Electronics Inc-IA Div
Quantity:
135
Part Number:
H7CX-AD-N DC12-24
Manufacturer:
Omron Electronics Inc-IA Div
Quantity:
135
Part Number:
H7CX-AS-N AC100-240
Manufacturer:
Omron Electronics Inc-IA Div
Quantity:
135
I Characteristics
Note: 1. To meet UL listing requirements with the H7CX-A11@ models, an OMRON P2CF-11-@ or P3GA-11 Socket must be mounted on the
Insulation resistance
Dielectric strength
Impulse withstand
voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Life expectancy
Approved safety
standards
(See note 1.)
EMC
Degree of protection
Weight
2. A waterproof packing is necessary to ensure IP66 waterproofing between the H7CX and installation panel.
H7CX. Otherwise, H7CX-A11@ models are considered to meet UL508 recognition requirements.
item
100 MΩ min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and be-
tween non-continuous contacts
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
2,000 VAC (for 100 to 240 VAC), 50/60 Hz for 1 min between power supply and input circuit (1,000 VAC for 24 VAC/
12 to 24 VDC)
1,000 VAC (for H7CX-@SD/-@SD1), 50/60 Hz for 1 min between control output, power supply, and input circuit
(2,000 VAC for models other than H7CX-@SD/-@SD1)
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC and 12 to 24 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC,
1.5 kV for 24 VAC/12 to 24 VDC and 12 to 24 VDC
±1.5 kV (between power terminals) for 100 to 240 VAC and 24 VAC/12 to 24 VDC, ±480 V for 12 to 24 VDC
±600 V (between input terminals)
Square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Destruction: 15 kV
Malfunction: 8 kV
Destruction: 10 to 55 Hz with 0.75-mm single amplitude, four cycles each in three directions (8 minutes per cycle)
Malfunction: 10 to 55 Hz with 0.35-mm single amplitude, four cycles each in three directions (8 minutes per cycle)
Destruction: 294 m/s
Malfunction: 98 m/s
Mechanical: 10,000,000 operations min.
Electrical:
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P100 (finger protection).
(EMI)
Emission Enclosure:
Emission AC mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance: EN61000-4-6:
Immunity Burst:
Immunity Surge:
Immunity Voltage Dip/Interruption
Panel surface: IP66 and NEMA Type 4 (indoors) (See note 2.)
Approx. 140 g
100,000 operations min. (3 A at 250 VAC, resistive load)
See Life-test Curve on page 92.
2
2
each in three directions
each in three directions
EN61326
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61326
EN61000-4-2:
EN61000-4-3:
EN61000-4-4:
EN61000-4-5:
EN61000-4-11: 0.5 cycle, 100% (rated voltage)
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated, 900 MHz ±5 MHz) (level 3)
10 V (0.15 to 80 MHz) (level 3)
2 kV power-line (level 3);
1 kV I/O signal-line (level 4)
1 kV line to lines (power and output lines) (level 2);
2 kV line to ground (power and output lines) (level 3)
Multifunction Preset Counter
H7CX
H7CX
C-91

Related parts for H7CX