P48-55-00 SYSTEMSENSOR [Systemsensor advanced ideas.], P48-55-00 Datasheet

no-image

P48-55-00

Manufacturer Part Number
P48-55-00
Description
4-Wire Ionization Duct Smoke Detector
Manufacturer
SYSTEMSENSOR [Systemsensor advanced ideas.]
Datasheet
4-Wire Ionization
Duct Smoke Detector
System Sensor’ s Innovair DH100ACDCI reduces the
spread of smoke through HVAC air handling systems.
As an ionization duct detector, it’ s ultra-responsive to
submicron-sized smoke particles typically found near
a fire source.
The DH100ACDCI senses smoke in velocities from 500 to 4,000 feet
per minute. When smoke is detected, all interconnected Innovairs
will initiate their relays. However, to quickly locate the fire source,
only the detector sensing smoke will alarm. Two DPDT Form-C relay
contacts, connected to auxiliary equipment, can also be configured
to prevent the spread of smoke through a particular area.
Beyond its reliable performance, the DH100ACDCI is simple to install
and maintain. Powered by 24 VAC/DC or 120/240 VAC, it can be easily
mounted to round and rectangular ducts, from one to twelve feet
in width, with outside mounting tabs. It also offers an adjustable
telescopic sampling tube that can be used for duct widths up to 18
inches. The tube locks into place – no additional tools are necessary.
Its modular construction allows for easy cleaning and field
replacement of the power and sensor boards. Also simplifying
maintenance is a transparent cover that provides convenient visual
inspection. If the cover is removed, a patented cover-tamper trouble
signal gives a 7-minute delay before the panel or remote accessory is
notified of trouble.
At a remote location, the remote test station option ensures that
a detector is functioning properly, and the remote sounder/LED
indicator options signal if a detector is in alarm. However, the cover
does not need to be removed if a detector needs to be reset at the
detector. Simply push the built-in reset button.
WARNING: Duct smoke detectors are NOT a substitute for open
area smoke detectors, NOT a substitute for early warning detection
and NOT a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional information.
Features
Agency Listings
Ionization technology
An air velocity rating from 500 feet per minute to 4,000 feet per
minute (2.54 meters per second to 20.32 meters per second)
Patented interconnectability for multi-fan shutdown
Two DPDT Form-C relay contacts
24 VAC/DC or 120/240 VAC
Versatile mounting options
Outside mounting tabs
A patented telescopic sampling tube
Modular construction
A patented cover-tamper trouble signal
A transparent cover
A remote test station
Remote sounder/LED indicator options
A built-in reset button
268A

Related parts for P48-55-00

P48-55-00 Summary of contents

Page 1

Ionization Duct Smoke Detector System Sensor’ s Innovair DH100ACDCI reduces the spread of smoke through HVAC air handling systems ionization duct detector, it’ s ultra-responsive to submicron-sized smoke particles typically found near a fire source. The DH100ACDCI ...

Page 2

Innovair Duct Smoke Detector Specifications Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor Model DH100ACDCI Series Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. ...

Page 3

Wiring Guide System wiring diagram for 4-wire duct smoke detectors + – Wiring diagram for the DH100ACDCI to RTS451/ RTS451KEY and interconnect feature: DH100ACDCI RTS451/RTS451KEY (Red LED) Alarm Alarm Signal 15 1 Aux. Power + 19 (Green LED) 6 Power ...

Page 4

... Metal sampling tube duct widths 2´–4´ (0.6–1.2 m) ST-5 Metal sampling tube duct widths 4´–8´ (1.2–2.4 m) ST-10 Metal sampling tube duct widths 8´–12´ (2.4–3.7 m) T80-71-00 Replacement telescoping sampling tube P48-55-00 Replacement end cap for T80-71-00 SSK451 Multi-signaling accessory RTS451KEY Remote test station with key lock RTS451 ...