SSV120-6 SYSTEMSENSOR [Systemsensor advanced ideas.], SSV120-6 Datasheet - Page 2

no-image

SSV120-6

Manufacturer Part Number
SSV120-6
Description
Alarm Bells
Manufacturer
SYSTEMSENSOR [Systemsensor advanced ideas.]
Datasheet
SSM/SSV Specifications
* Sound output measured at Underwriter Laboratories, as specifi ed in UL464
Ordering Information
Architectural/Engineering Specifi cations
Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than
nominal 6˝/8˝/10˝ (specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi-fl ush
mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to
a standard 4˝ square electrical box having a maximum projection of 2½˝. Bells shall be located as shown on the drawings or as determined by the Authority
Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory
Mutual and MEA.
Physical/Operating Specifi cations
Operating Temperature Range
Operating Voltage
Termination
Service Use
Warranty
UL/FM Model No.
SSM24-6
SSM24-8
SSM24-10
SSV120-6
SSV120-8
SSV120-10
WBB
Electrical Specifi cations
Model
SSM24-6
SSM24-8
SSM24-10
SSV120-6
SSV120-8
SSV120-10
Gong Diameter
(inches)
6
8
10
6
8
10
ULC/Canadian Model No.
SSM24-6A
SSM24-8A
SSM24-10A
SSV120-6A
SSV120-8A
SSV120-10A
Nominal Voltage
Regulated 24VDC
Regulated 24VDC
Regulated 24VDC
Regulated 120VAC
Regulated 120VAC
Regulated 120VAC
–31°F to 140°F
SSM series: 24 VDC
SSV series: 120 VAC
Provided with 2 sets of leads for in/out wiring
Fire Alarm, General Signaling, Burglar Alarm
3 years
Phone: 800-SENSOR2 • Fax: 630-377-6495
3825 Ohio Avenue • St. Charles, IL 60174
Description
Bell, 6˝, 24VDC, Polarized, 82dBA
Bell, 8˝, 24VDC, Polarized, 80dBA
Bell, 10˝, 24VDC, Polarized, 81dBA
Bell, 6˝, 120VAC, 85dBA
Bell, 8˝, 120VAC, 82dBA
Bell, 10˝, 120VAC, 82dBA
Weatherproof back box for SSM and SSV series, when installed outdoors
Operating Voltage
Limit
16 to 33VDC
16 to 33VDC
16 to 33VDC
96 to 132VAC
96 to 132VAC
96 to 132VAC
Maximum Current
DC-31.1mA/ FWR-53.5mA
DC-31.1mA/ FWR-53.5mA
DC-31.1mA/ FWR-53.5mA
53mA
53mA
53mA
Product specifi cations subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0260-008 • 4/07 • #1676
©2007 System Sensor.
Sound Output (dBA)
82
80
81
85
82
82