k3hb-s Omron Corporation, k3hb-s Datasheet - Page 3

no-image

k3hb-s

Manufacturer Part Number
k3hb-s
Description
Linear Sensor Indicator
Manufacturer
Omron Corporation
Datasheet
■ Characteristics
■ Input Ranges (Measurement Ranges and Accuracy)
Note: The accuracy is for an ambient temperature of 23±5°C.
Display range
Sampling period
Comparative out-
put response
times (transistor
outputs)
Linear output re-
sponse time
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Weight
Degree of protec-
tion
Memory protection
Applicable standards
EMC
K3HB-SSD
DC voltage/current
input
Input
One input
Two inputs
One input
Two inputs
Front panel
Rear case
Terminals
0 to 20 mA
4 to 20 mA
0 to 5 V
1 to 5 V
±5 V
±10 V
Input type
0.000 to 20.000 mA
4.000 to 20.000 mA
0.000 to 5.000 V
1.000 to 5.000 V
±5.000 V
±10.000 V
−19,999 to 99,999
One input: 0.5 ms; Two inputs: 1.0 ms
OFF to ON: 1 ms max., ON to OFF: 1.5 ms max.
(The time until the comparative output is output when there is a forced sudden change in the input signal from 15% to 95%
or 95% to 15%.)
OFF to ON: 2 ms max., ON to OFF: 2.5 ms max.
(The time until the comparative output is output when there is a forced sudden change in the input signal from 15% to 95%
or 95% to 15%.)
51 ms max.
(The time until the final analog output is reached when there is a forced sudden change in the input signal from 15% to
95% or 95% to 15%.)
52 ms max.
(The time until the final analog output is reached when there is a forced sudden change in the input signal from 15% to
95% or 95% to 15%.)
20 MΩ min. (at 500 VDC)
2,300 VAC for 1 min between external terminals and case
100 to 240 VAC models:
24 VAC/VDC models:
Frequency: 10 to 55 Hz; Acceleration: 50 m/s
150 m/s
Approx. 300 g (Base Unit only)
Conforms to NEMA 4X for indoor use (equivalent to IP66)
IP20
IP00 + finger protection (VDE0106/100)
EEPROM (non-volatile memory)
Number of rewrites: 100,000
UL61010C-1, CSA C22.2 No. 1010.1(evaluated by UL)
EN61010-1 (IEC61010-1): Pollution degree 2/Overvoltage category II
EN61326: 1997, A1: 1998, A2: 2001
EMI: EN61326 industrial applications
Electromagnetic radiation interference
Terminal interference voltage
EMS: EN61326 industrial applications
Electrostatic Discharge Immunity
Radiated Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
Conducted Disturbance Immunity
Power Frequency Magnetic Immunity
Voltage Dips and Interruptions Immunity
Measurement range
±1,500 V at power supply terminals in normal or common mode
(waveform with 1-ns rising edge and pulse width of 1 µs/100 ns)
±1,500 V at power supply terminals in normal or common mode
(waveform with 1-ns rising edge and pulse width of 1 µs/100 ns)
CISPR 11 Group 1, Class A
CISPR 11 Group 1, Class A
EN61000-4-2: 4 kV (contact), 8 kV (in air)
EN61000-4-3: 10 V/m 1 kHz sine wave amplitude modulation (80 MHz to 1 GHz, 1.4 to 2 GHz)
EN61000-4-4: 2 kV (power line), 1 kV (I/O signal line)
EN61000-4-5: 1 kV with line (power line), 2 kV with ground (power line)
EN61000-4-6: 3 V (0.15 to 80 MHz)
EN61000-4-8: 30 A/m (50 Hz) continuous time
EN61000-4-11: 0.5 cycle, 0°/180°, 100% (rated voltage)
2
(100 m/s
2
for relay outputs) 3 times each in 3 axes, 6 directions
−2.000 to 22.000 mA
2.000 to 22.000 mA
−0.500 to 5.500 mA
0.500 to 5.500 V
±5.500 V
±11.000 V
Indication range
2
, 10 sweeps of 5 min each in X, Y, and Z directions
120 Ω max.
1 MΩ min.
impedance
Input
One input:
±
±1 digit max.
Two inputs:
±
±
0.1% F.S.
0.2% F.S.
1 digit max.
(at 23±5°C)
Accuracy
±31 mA
±10 V
±14.5 V
absolute rated
K3HB-S
Maximum
input
3

Related parts for k3hb-s