PowerFlex 40P Technical Data
Parameter List
Parameter
Number
Basic Display Group
b001
b002
b003
b004
b005
b006
b007
b008
b009
b010
b012
b013
b014
b015
b016
b017
b018
b019
b020
b021
b022
b023
b024
b025
b026
b028
b029
Basic Program Group
P031
P032
P033
P034
P035
P036
P037
P038
P039
P040
P041
P042
P043
Advanced Program Group
A051
A052
A053
A054
A055
A056
A058
A059
A061
Parameter Name
Output Freq
Commanded Freq
Output Current
Output Voltage
DC Bus Voltage
Drive Status
Fault 1 Code
Fault 2 Code
Fault 3 Code
Process Display
Control Source
Contrl In Status
Dig In Status
Comm Status
Control SW Ver
Drive Type
Elapsed Run Time
Testpoint Data
Analog In 0-10V
Analog In 4-20mA
Output Power
Output Powr Fctr
Drive Temp
Counter Status
Timer Status
Stp Logic Status
Torque Current
Motor NP Volts
Motor NP Hertz
Motor OL Current
Minimum Freq
Maximum Freq
Start Source
Stop Mode
Speed Reference
Accel Time 1
Decel Time 1
Reset To Defalts
Voltage Class
Motor OL Ret
Digital In1 Sel
Digital In2 Sel
Digital In3 Sel
Digital In4 Sel
Relay Out Sel
Relay Out Level
Opto Out1 Sel
Opto Out1 Level
Opto Out2 Sel
Description
Output frequency present at T1, T2 & T3 (U, V & W).
Value of the active frequency command.
Output current present at T1, T2 & T3 (U, V & W).
Output voltage present at T1, T2 & T3 (U, V & W).
Present DC bus voltage level.
Present operating condition of the drive.
A code that represents a drive fault.
Output frequency scaled by A099 [Process Factor].
Displays the active source of the Start Command and Speed Command.
Status of the control terminal block control inputs.
Status of the control terminal block digital inputs.
Status of the communication ports.
Main Control Board software version.
Used by Rockwell Automation field service personnel.
Accumulated time drive is outputting power.
Present value of the function selected in A102 [Testpoint Sel].
Present value of the voltage at I/O Terminal 13.
Present value of the current at I/O Terminal 15.
Output power present at T1, T2 & T3 (U, V & W).
The angle in electrical degrees between motor voltage and motor current.
Present operating temperature of the drive power section.
The current value of the counter when counter is enabled.
The current value of the timer when timer is enabled.
The current step of the StepLogic profile.
The current value of the motor torque current.
20 to Drive Rated Volts
15 to 500 Hz
0.0 to (Drive Rated Amps x 2)
0.00 to 500.0 Hz
0.00 to 500.0 Hz
6 settings; 3-Wire, 2-Wire, 2-W Lvl Sens, 2-W Hi Speed, Comm Port, Momt FWD/REV
10 settings: Ramp, CF; Coast, CF; DC Brake, CF; DCBrkAuto,CF; Ramp; Coast; DC Brake;
DC BrakeAuto; Ramp+EM B,CF; Ramp+EM Brk
9 settings; InternalFreq, 0-10V Input, 4-20mA Input, Preset Freq, Comm Port, Stp Logic,
Anlg In Mult, Encoder, Positioning
0.0 to 600.0 seconds
0.0 to 600.0 seconds
Used to reset drive to factory default settings.
Sets the voltage class of 600V drives.
Enables/disables the Motor Overload Retention function.
36 settings: Not Used; Acc/Dec Sel1; Jog; Aux Fault; Preset Freq; Comm Port;
Clear Fault; RampStop,CF; CoastStop,CF; DCInjStop,CF; Jog Forward; Jog Reverse;
10V In Ctrl; 20mA In Ctrl; PID Disable; MOP Up; MOP Down; Timer Start; Counter In;
Reset Timer; Reset Countr; Rset Tim&Cnt; Logic In1; Logic In2; Current Lmt2; Anlg Invert;
EM Brk Rlse; Acc/Dec Sel2; Precharge En; Inertia Dcel; Sync Enable; Traverse Dis; Home
Limit; Find Home; Hold Step; Pos Redefine
26 settings; Ready/Fault, At Frequency, MotorRunning, Reverse, Motor Overld, Ramp Reg,
Above Freq, Above Cur, Above DCVolt, Retries Exst, Above Anlg V, Logic In 1, Logic In 2,
Logic 1 & 2, Logic 1 or 2, StpLogic Out, Timer Out, Counter Out, Above PF Ang, Anlg In Loss,
ParamControl, NonRec Fault, EM Brk Cntrl, At Position, At Home, Safe-Off
0.0 to 9999
26 settings; Ready/Fault, At Frequency, MotorRunning, Reverse, Motor Overld, Ramp Reg,
Above Freq, Above Cur, Above DCVolt, Retries Exst, Above Anlg V, Logic In 1, Logic In 2,
Logic 1 & 2, Logic 1 or 2, StpLogic Out, Timer Out, Counter Out, Above PF Ang, Anlg In Loss,
ParamControl, NonRec Fault, EM Brk Cntrl, At Position, At Home, Safe-Off
0.0 to 9999
26 settings; Ready/Fault, At Frequency, MotorRunning, Reverse, Motor Overld, Ramp Reg,
Above Freq, Above Cur, Above DCVolt, Retries Exst, Above Anlg V, Logic In 1, Logic In 2,
Logic 1 & 2, Logic 1 or 2, StpLogic Out, Timer Out, Counter Out, Above PF Ang, Anlg In Loss,
ParamControl, NonRec Fault, EM Brk Cntrl, At Position, At Home, Safe-Off
Factory Default
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Based on Drive Rating
60 Hz
Based on Drive Rating
0.00 Hz
60.00 Hz
Comm Port
Ramp, CF (Clear Fault)
Comm Port
10.0 Secs
10.0 Secs
Ready/Idle
High Voltage
Disabled
Preset Freq
Preset Freq
Local
Jog Forward
Ready/Fault
0.0
MotorRunning
0.0
At Frequency
25