PNOZX4 PILZ, PNOZX4 Datasheet

86H2640

PNOZX4

Manufacturer Part Number
PNOZX4
Description
86H2640
Manufacturer
PILZ
Datasheet

Specifications of PNOZX4

Coil Voltage Vac Nom
240V
Coil Voltage Vdc Nom
24V
Contact Current Max
8A
Contact Voltage Ac Nom
240V
Contact Voltage Dc Nom
24V
Contact Configuration
3PST-NO / SPST-NC
No. Of Poles
4
Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X4
EMERGENCY STOP switchgear and
safety gate monitor according to
VDE 0113-1, 11/98, EN 60204-1,
12/97 and IEC 60204-1, 11/98
Approvals
Features
● either monitored, unmonitored
● 1-channel or 2-channel wiring
or automatic start possible
with or without shorts across
contacts detection
PNOZ X4
Description
● 45 mm P-97 housing, on standard
● Relay outputs, positive-guided:
● Connection possibilities for
● LEDs for switching status
● Contact multiplication and
Technical data
Electrical data
Power supply
Tolerance
Power consumption
Voltage and current at input,
start and feedback loop
Output contacts
Switching capability according to
EN 60947-4-1, 02/01
EN 60947-5-1, 11/97 (DC13:6 cycles/min)
Contact protection according to
EN 60947-5-1, 08/00
Times
Pickup delay
Delay-on de-energisation
Recovery time
Simultaneity channel 1 and 2
Power failure buffer
Mechanical data
Max. cross-section of outer conductor
single wire or multi-wire with
end ferrule
Dimensions (H x W x D)
Weight
rail, snap-on
– 3 safety contacts (NO)
– 1 auxiliary contact (NC)
– EMERGENCY STOP switch
– Safety gate limit switch
– Start switch
Channel 1 and 2 and power
supply
Contact amplification possible by
external contactors
monitored start: max. 100 ms
2 x 1.5 mm
PNOZ X4
AC: 24, 110, 115, 120, 230, 240 V
DC: 24 V
85 ... 110 %
Approx. 4.5 VA/2.5 W
24 V DC, 40 mA
3 safety contacts (NO)
1 auxiliary contact (NC)
AC1: 240 V/8 A/2000 VA
DC1: 24 V/8 A/200 W
AC15: 230 V/5 A; DC13: 24 V/7 A
10 A quick or 6 A slow
auto./man. start: max. 0,35 s
at EMERGENCY STOP: max. 50 ms
at mains off: max. 0,5 s
approx. 1 s
¥
approx. 25 ms
87 x 45 x 121 mm
AC: 360 g, DC: 265 g
Operating modes
● Single channel mode
● Dual channel mode without shorts
● Dual channel mode with shorts
● Automatic start
● Manual start without monitoring
● Manual start with monitoring
across contacts detection
across contacts detection
2
oder 1 x 2.5 mm
NSG-D-2-128-12/01
2
1

Related parts for PNOZX4

PNOZX4 Summary of contents

Page 1

... Emergency Stop Relays, Safety Gate Monitors Category 4, EN 954-1 PNOZ X4 EMERGENCY STOP switchgear and safety gate monitor according to VDE 0113-1, 11/98, EN 60204-1, 12/97 and IEC 60204-1, 11/98 Features ● either monitored, unmonitored or automatic start possible ● 1-channel or 2-channel wiring with or without shorts across ...

Page 2

... Emergency Stop Relays, Safety Gate Monitors Category 4, EN 954-1 PNOZ X4 Schematic interior diagram Feedback- Start Rückführ- Start- loop loop U B kreis kreis S34 S33 S52 AC DC Start loop Startkreis Channel Kanal 2 2 S21 S22 Y36 Y37 Only on AC nur am Input loop AC-Gerä ...

Page 3

... Emergency Stop Relays, Safety Gate Monitors Category 4, EN 954-1 PNOZ X4 ● Contact multiplication The output contacts can be amplified or multiplied by external contactors with positive-guided contacts if necessary. 1L1 1L2 1 NSG-D-2-128-12/01 ...

Page 4

... Emergency Stop Relays, Safety Gate Monitors Category 4, EN 954-1 PNOZ X4 General Technical Data Unless stated otherwise in the technical details for the specific unit Electrical Data Frequency Range AC Residual Ripple DC Contact Material Continuous Duty Environmental Data EMC Vibration in accordance with EN 60068-2-6, 01/00 ...

Related keywords