CR9421-ACA CR Magnetics Inc, CR9421-ACA Datasheet

no-image

CR9421-ACA

Manufacturer Part Number
CR9421-ACA
Description
SWITCH CURRENT AC NC .27" DIA.
Manufacturer
CR Magnetics Inc
Series
CR9400r
Datasheet

Specifications of CR9421-ACA

Current - Sensing
100A
Accuracy
-
Sensitivity
-
Current - Supply
-
Sensor Type
Switch
Voltage - Supply
-
Output
SCR/NO
Frequency
50Hz ~ 400Hz
Response Time
250ms
Polarization
Bidirectional
Operating Temperature
-30°C ~ 60°C
Package / Case
Ring, 0.27" Dia, Wire Leads
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Another HUNTINGTON ELECTRIC Company
On state current: 0.8 AAC RMS max. continuous
Off state leakage: 50 ua @ 240 VAC max.
ELECTRICAL CONNECTIONS
CR9421 Outline Drawing
Minimum switch voltage: 24 VAC RMS
Off state voltage: 240 VAC RMS max.
Peak Non-Repetitive Surge Current:
AC SWITCHING (-ACA)
1.614(41)
1.775 (45)
CR9521
CR9550
CR9421
CR9450
OUTLINE DRAWING
8 AAC RMS (1 cycle, 60 Hz.)
(MM)
IN
0.875
(22.2)
1.062
(27)
-ACA
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
BLACK
BLACK
0.27 (6.8) DIA. CR9521
0.61 (15.5) DIA. CR9550
VAC
49.57 mm
36.86 mm
+
-
CR9480
1.95
AWG #22, 12 (304) LONG
1.45
(22.2)
0.875
CR9421
CR9450
25.42 mm
1.00
0.40
10.17 mm
23.39 mm
0.92
24.91 mm
0.98
0.40
10.17 mm
50.84 mm
2.00
The CR9400 Series is a low cost, self powered, fixed set-point Current
Switch designed for applications that require an on-off indication of
current flow.
The normal state of the switch is On when the current level is zero. Cur-
rent levels above the guaranteed full-off level will turn the output to Off.
The Current Switch is recommended only for applications where the
continuous operating level is above the rated full on level of 350 mA.
Operation below this point will not drive the output device full-on and
derate the output ratings.
The unit available with a SCR output for switching AC. Connections can
be made directly to items such as a PLC or electro-mechanical relay.
Note that connections made directly to an inductive device such as an
electro-mechanical relay will require a customer supplied clamping
diode for DC operation or a snubber network for AC operation.
Applications
Continuity
Proving Switch
Features
Low Cost
Low Fixed Trip Point
Fully Isolated
Self-Powered
Specifications
Rated Full-off: 0.350 AAC RMS
Turn-on Time: 100 ms. max. @ rated full-on
Turn-off Time: 250 ms. max. to 80% of Vce
Maximum sense current: Continuous: 100 AAC
Frequency*: 50 to 400 Hz
Operating Temperature: -30° C to +60° C
Storage Temperature: -55° C to +85° C
Weight 0.08 LBS.
*All specifications for operation at 60 Hz only
Regulatory Agencies
CR
9421 .27 dia. Window
9450 .61 dia. Window
9480 .49 Splitcore
77
Current Switch - Normally Closed
-
PART NUMBER
ACA AC Output
1 Second: 500 AAC
-
E-mail: sales@crmagnetics.com
M Mounting Case
CURRENT SWITCH
(optional)
CR9400 Series
E