Basic Concepts
3-1
88
Basic Concepts
• The communications power supply must be 24 V DC.
• Always supply the power from the trunk line.
• When providing power to several nodes from one power supply, try to
• Provide power through Power Supply Taps. It is possible to use a T-
• The power supply capacity for cables is restricted to 8 A for Thick Cables,
• Environment-resistive Slaves are wired with Thin Cable, so the current
• A single network is usually supplied by one power supply, however, it is
• Provide some extra power supply capacity in the network to allow for
• Turning OFF the communications power supply during operation can
• The current capacity of a branch line ranges from 0.75 to 3 A, depending
locate the power supply near the center of the nodes.
branch Tap or T-branch Connector instead of a Power Supply Tap when
there is one communications power supply in the system and the current
consumption is within the specifications of the T-branch Tap or T-branch
Connector. Refer to 2-3-4 T-branch Taps or 2-3-5 Shielded T-branch Con-
nectors for details on the current limitations of these components.
3 A for Thin Cables, and 5 A for Flat Cables.
through a cable to an Environment-resistive Slave is limited to 3 A.
possible to have more than one power supply when power supply require-
ments cannot be met with a single power supply. (See 3-6 Step 3: Split-
ting the System into Multiple Power Supplies.)
future expansion and extend the life of the power supply.
cause errors in the other nodes if the other power supplies are left ON.
on its length. Use the following equation to calculate the current capacity.
(The maximum current capacity of a branch line is 3 A, even if the branch
line is shorter than 1.53 m.)
I = 4.57/L
I: Permissible current (A)
L: Length of the branch line (m)
Section 3-1