SU2200XLNET APC, SU2200XLNET Datasheet - Page 21

no-image

SU2200XLNET

Manufacturer Part Number
SU2200XLNET
Description
UPS - Uninterruptible Power Supplies APC Smart-UPS XL 2200VA 120V
Manufacturer
APC
Datasheet

Specifications of SU2200XLNET

Power Rating
1600 W
Output Voltage Rating
120 V
Number Of Outlets
8
Interface Port
DB-9 RS-232, SmartSlot
Topology
Online
Tower / Rackmount
Tower
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Unit will not turn on.
Unit will not turn on or
off.
Unit operates on-battery
even though normal line
voltage is thought to
exist.
Unit beeps occasionally.
Unit does not provide
expected back up time.
Front panel indictors
flash sequentially.
All indicators are lit and
the unit emits a constant
tone.
8. Troubleshooting
Problem
On/test button not
pushed.
Unit’s input circuit breaker
tripped.
Very low or no utility
voltage.
Computer interface or
accessory problem.
Unit’s input circuit breaker
tripped.
Very high, low, or
distorted line voltage.
Normal operation.
The unit’s battery is weak
due to recent outage or is
near the end of its service
life.
The unit is overloaded.
The unit has been shut
down by remote control.
Internal unit fault.
Possible Cause
Press the on/test button to power the unit
and the load
Reduce the load on the unit by unplugging
equipment and reset the circuit breaker by
pressing the plunger back in.
Check the AC power supply to the unit
with a table lamp. If very dim, have the
utility voltage checked.
Disconnect the computer interface or
accessory. If the unit now works normally,
check the interface cable, the attached
computer, and the accessory.
Reduce the load on the unit by unplugging
equipment and reset the circuit breaker.
Test the input voltage with the utility
voltage display. See section 5.6. Inexpensive
fuel powered generators can distort the
voltage. If acceptable to the load, reduce
the unit’s sensitivity. See section 5.9.
None. The unit is protecting the load.
Charge the battery. The unit"s batteries
require recharging after an extended
outage. Batteries wear faster when put into
service often and when operated at
elevated temperatures. If the battery is near
the end of its service life, consider
replacing the battery even if the replace
battery indicator is not yet lit.
Check the unit’s load display. See section
5.4. Unplug less needed equipment, such as
printers.
None. The unit will restart automatically
when utility power returns.
Do not attempt to use the unit.. Turn the
unit off and have it serviced immediately.
Solution
17