Description
Sensor, Current; 200A Pri:20 to 100Hz; 4 to 20mA (DC); +/-0.5%; UL Listed; 3.5In.L
Manufacturer
Pacific Scientific OECO
Type
Inductiver
Datasheet

Specifications of PCS-200

Accuracy
± 0.5 %
Brand/series
PCS
Current, Primary
200 A (RMS)
Current, Secondary
4 to 20 mA (DC)
Current, Switching
20 mA
Frequency Response
20 to100 Hz
Function
Current
Height
4.22 in.
Length
3.5 in.
Mounting Type
Panel
Output
Current
Primary Type
Current
Range, Measurement
200 A
Standards
UL Listed
Technology
Inductive
Voltage, Supply
40 VDC
Width
0.071 in.
Lead Free Status / Rohs Status
RoHS Compliant part
Model PC and PCS
AC Current Sensors
Description
The PC/PCS Series current sensors accurately measure
sinusoidal AC current and provide a 4-20 mA DC output
proportional to the RMS value. They are loop powered
requiring only a two wire connection. The PCS-50 and
PCS-200 clamp over existing wiring for easy installation.
Features
• UL Listed • Loop Powered • Range Selected on Sensor
• Only Requires Two Wire Connection • Features Split Core for Easy Installation
Electrical Specifications
Current Range (1) .............. A AC rm s
Output (2) ......................... mA DC
Frequency Range ................ Hz
Suppl y Voltage (3) .............. VDC
Accuracy ........................... +% Full Scale (FS)
Repeatability ...................... +% FS
Linearity ............................ +% FS
Response time (Max.) ......... m s
Ripple and Noise (Max.) ...... mV Peak to Peak
Output Current Limit (4) ..... m A
Internal Protection ..............
Dielectric test (6) ................ kV
General Information
Operating Temperature (5) ...
Aperture Opening ............... inches (mm)
Weight ............................. grams
Mounting ..........................
Package ...........................
Notes:
1. Refer to Table 1 for choice of current ranges.
2. Refer to Table 2
3. Minimum voltage is 5 volts (for the sensor) plus voltage dropped across total load resistance when sensor is at 20 mA. Example: 20
4. Sensor self-limits output current to 40 mA maximum.
5. The UL approval is for an operating temperature range of -10
6. The dielectric test consists of 5.0 kVac 60 Hz for one minute between a bare 0.8 inch diameter conductor (located concentrically
through the aperture) and the output of the sensor.
mA will drop 16 volts across 800 ohms total load resistance. 16 volts plus 5 volts equals 21 volts minimum requirement.
O
Units
C
o
C to +40
Reverse voltage protection, High over-current capability
ABS plastic case meets UL f lammability rating 94V - 0
0.73 (18.5)
PC-50
o
C.
0.1
92
50
Panel mount via two #6 screws
PC-200
20 to 100
0.73 (18.5)
-20 to +50
40 Max.
4 to 20
5 to 40
0.5
0.1
0.1
300
200
92
5
8
Current Sensors
PCS-50
0.85 (21.6)
0.3
50
121
PCS-200
0.85 (21.6)
200
0.3
121

Related parts for PCS-200

PCS-200 Summary of contents

Page 1

... AC current and provide a 4- output proportional to the RMS value. They are loop powered requiring only a two wire connection. The PCS-50 and PCS-200 clamp over existing wiring for easy installation. Features • UL Listed • Loop Powered • Range Selected on Sensor • Only Requires Two Wire Connection • Features Split Core for Easy Installation ...