CS-150 Pacific Scientific OECO, CS-150 Datasheet

no-image

CS-150

Manufacturer Part Number
CS-150
Description
Sensor, Current; 1 to 150A Pri:6 to 100Hz; Screw; Panel; 0.73In.Dia.; UL Listed; 3.5In
Manufacturer
Pacific Scientific OECO
Type
Hall Effectr
Datasheet

Specifications of CS-150

Current, Primary
1 to 150 A
Current, Switching
0.3 A
Diameter, Inside
0.73 in.
Frequency Response
6 to 100 Hz
Function
Current
Height
4.22 in.
Length
3.5 in.
Mounting Type
Panel
Primary Type
Current
Range, Measurement
150 A
Standards
UL Listed
Technology
Hall Effect
Termination
Screw
Voltage, Switching
135 VAC/VDC
Width
0.071 in.
Lead Free Status / Rohs Status
RoHS Compliant part
Model CS-150 and CSS-150
Description
The Models CS-150 and CSS-150 detect AC current from 1 to 150 amps and provide a solid state
switched output when the current exceeds the adjustable trip point. Adjustment is made by a
multi-turn trim pot. A flashing LED gives visual indication of the trip point. The CSS-150 clamps
over existing wiring for easy installation. UL listed.
Features
· Adjustable trip range from 1 A to 150 A
· Simple two wire connection
· Split core for easy installation
· Built in LED indicates On/Off status
· Switch rated 1 to 135 volts AC or DC
Applications
· Sense broken belts on motors
· Detect open heater strips
· Sense clogged air filters
· Detect burned out navigation lights
· Operational status of fans, motors and pumps.
Electrical Specifications
Detection Range .............................................
Hysteresis (Deadband)
Frequency Range .............................................
Switch contacts (Solid State)
Response Time (maximum) ...............................
Over-Range capability
UL Voltage rating ............................................
General Information
Operating Temperature .....................................
Aperture Opening ............................................. Inches(mm)
Notes:
2. The LED indicates thr ee possible operating states: Fast Flashing indicates power is on and sensor contacts are closed. Slow Flashing
Weight ............................................................ Grams
Mounting ........................................................
1. The output contacts are normally open. Contacts close when the current exceeds the set point. The output contacts can accept AC or DC
(split core - 1.5 A to 150 A)
1000 A ......................................................
Maximum Current ........................................
and are not polarity sensitive.
indicates power is on, but sensor is below trip point and No Flashing indicates power is off or below minimum range of sensor.
1 A setting ................................................
50 A setting ..............................................
150 A setting ............................................
Voltage Rang e ...........................................
400 A ......................................................
seconds
seconds
A AC/DC
ms
V
Units
Amps
mA
Amps
Amps
Hz
V AC/DC
O
C
Open Loop Hall Effect
0.73 (18.5) DIA.
CS-150
1 - 150
98
Panel mount via two #6 screws
-50 to +65
6 to 100
1 to 135
1,250
250
2.5
7.5
0.3
50
6
1
+0.85 (21.6)
CSS-150
1.5 - 150
121

Related parts for CS-150

CS-150 Summary of contents

Page 1

... Model CS-150 and CSS-150 Description The Models CS-150 and CSS-150 detect AC current from 1 to 150 amps and provide a solid state switched output when the current exceeds the adjustable trip point. Adjustment is made by a multi-turn trim pot. A flashing LED gives visual indication of the trip point. The CSS-150 clamps over existing wiring for easy installation ...

Page 2

... Sensor in series with power source 135 VOLTS MAXIMUM 3.000 (76.20) .190 DIA. .437 (4.83) (11.10) (2-PLCS.) .590 (14.99) TRIP .437 TYP. L.E.D. POINT (11.10) ADJ. 2.400 (60.96) 1.752 (44.50) .510 (12.95) 3.500 (88.90) RELAY CONTACTOR INDICATOR LIGHT ETC. CS-150 CSS-150 ...

Related keywords