Description
OPERATOR INTERFACE; COLOR TFT LCD; 10 INCH; 24V; 8MB FLASH MEMORY
Manufacturer
Red Lion Controls
Type
Color Graphicr
Datasheet

Specifications of G310C000

Dimensions
12.83 W × 9.5 H In.
Display Size
10 In.
Memory
8 Mb Flash
Mounting Type
Panel
Primary Type
Operator Interface
Resolution
640 × 480 Pixel LCD
Resolution, Display
640 × 480
Size
10 In. Color TFT
User Interface
Touchscreen
Voltage, Supply
24 V
Lead Free Status / Rohs Status
RoHS Compliant part
1. POWER REQUIREMENTS:
2. BATTERY: Lithium coin cell. Typical lifetime of 10 years.
3. LCD MODULE DISPLAYS:
*Lifetime at room temperature. Refer to “Display” in the “Software/Unit
4. 8-KEY KEYPAD: for on-screen menus.
5. TOUCHSCREEN: Resistive analog
6. MEMORY:
7. COMMUNICATIONS:
8. ENVIRONMENTAL CONDITIONS:
S
DIMENSIONS In inches (mm)
G310C: +24 VDC ±20% @ 33 W maximum.
G310S: +24 VDC ±20% @ 50 W maximum.
Must use Class 2 or SELV rated power supply.
Power connection via removable three position terminal block.
Notes:
Operation” section.
On Board User Memory: 8 Mbyte of onboard non-volatile Flash memory.
Memory Card: CompactFlash Type II slot for Type I and Type II
USB Port: Adheres to USB specification 1.1. Device only using Type B
Serial Ports: Format and Baud Rates for each port are individually software
Ethernet Port: 10 BASE-T / 100 BASE-TX
Operating Temperature Range: 0 to 50°C
Storage Temperature Range: G310C: -20 to 70°C
Operating and Storage Humidity: 80% maximum relative humidity (non-
PECIFICATIONS
1. The front panel PWR LED indicates power.
2. The G310’s circuit common is not connected to the enclosure of the
CompactFlash cards.
connection.
programmable up to 115,200 baud.
PGM Port: RS232 port via RJ12.
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12.
DH485 TXEN: Transmit enable; open collector, V
Note: For additional information on the communications or signal
RJ45 jack is wired as a NIC (Network Interface Card).
condensing) from 0 to 50°C.
unit. See “Connecting to Earth Ground” in the section “Installing and
Powering the G310.”
V
common and connections to earth ground please see the “Connecting to
Earth Ground” in the section “Installing and Powering the G310.”
OL
SIZE
TYPE
COLORS
PIXELS
BRIGHTNESS
BACKLIGHT*
= 0.5 V @ 25 mA max.
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
MODEL
50,000 HR TYP.
640 X 480
450 cd/m
10.4-inch
256 VGA
G310C
TFT
G310S: -20 to 60°C
2
20,000 HR TYP.
640 X 480
850 cd/m
10.4-inch
256 VGA
G310S
TFT
2
OH
= 15 VDC,
2
9. CERTIFICATIONS AND COMPLIANCES:
10. CONNECTIONS: Compression cage-clamp terminal block.
11. CONSTRUCTION: Steel rear metal enclosure with NEMA 4X/IP66
12. MOUNTING REQUIREMENTS: Maximum panel thickness is 0.25" (6.3
13. WEIGHT: 5.53 lbs (2.51 Kg)
Vibration According to IEC 68-2-6: 10 to 55 Hz, in X, Y, Z direction for 1.5
Shock According to IEC 68-2-27: Operational 30 g, 9 msec in 3 directions.
Altitude: Up to 2000 meters.
SAFETY
UL Recognized Component, File #E179259, UL61010-1, CSA 22.2 No.61010-1
UL Listed, File #E211967, UL61010-1, UL1604, CSA 22.2 No. 61010.1,
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/9737C/UL,
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for
Notes:
Wire Gage: 12-30 AWG copper wire
Torque: 5-7 inch-pounds (56-79 N-cm)
aluminum front plate when correctly fitted with the gasket provided.
Installation Category II, Pollution Degree 2.
mm). For NEMA 4X/IP66 sealing, a steel panel with a minimum thickness of
0.125" (3.17 mm) is recommended.
Maximum Mounting Stud Torque: 17 inch-pounds (1.92 N-m)
Immunity to Industrial Locations:
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
Surge
RF conducted interference
Emissions:
Emissions
hours, 1 g.
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
CB Scheme Test Report #E179259-V01-S04
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP66 Enclosure rating (Face only), IEC 529
Measurement, Control and Laboratory use.
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-
Issued by Underwriters Laboratories Inc.
for measurement, control, and laboratory use, Part 1.
recovers.
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 55011
Criterion A
4 kV contact discharge
8 kV air discharge
Criterion A
10 V/m
Criterion A
2 kV power
2 kV signal
Criterion A
1 kV L-L,
Criterion B
3 V/rms
Class A
2 kV L&N-E power