ES1-LP3 Omron, ES1-LP3 Datasheet - Page 20

no-image

ES1-LP3

Manufacturer Part Number
ES1-LP3
Description
Sensor Hardware & Accessories INFRARED SENSOR 0-500 C
Manufacturer
Omron
Datasheets

Specifications of ES1-LP3

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
20
E5AZ/E5EZ
Characteristics
Note: 1. The indication accuracy of K thermocouples in the 200 to
Indication accuracy
Influence of tempera-
ture (See note 2.)
Influence of voltage
(See note 2.)
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Affect of signal source
resistance
Insulation resistance
Dielectric strength
Vibration
resis-
tance
Shock
resis-
tance
Weight
Degree of protection
Memory protection
EMC
Approved standards
Conformed standards
2. Conditions: Ambient temperature: 10 C to 23 C to 55 C,
3. “EU” stands for Engineering Unit and is used as the unit
4. B, R, and S sensors: 0.2 C/ max. (100
1300 C range, T and N thermocouples at a temperature of
temperature is 2 C 1 digit maximum. The indication
accuracy of the B thermocouple at a temperature of 400 C
max. is not specified. The indication accuracy of the R and
S thermocouples at a temperature of 200 C max. is 3 C 1
digit max.
Voltage range: 15% to +10% of rated voltage
after scaling. For a temperature sensor, the EU is C or F.
Malfunction
Destruction
Malfunction
Destruction
E5AZ
E5EZ
100 C max., and U and L thermocouples at any
Thermocouple: (See note 1.)
( 0.5% of indicated value or 1 C, whichever is greater) 1
digit max.
Platinum resistance thermometer:
( 0.5% of indicated value or 1 C, whichever is greater) 1
digit max.
Analog input: 0.5% FS 1 digit max.
CT input: 5% FS 1 digit max.
R, S, and B thermocouple inputs:
( 1% of PV or 10 C, whichever is greater) 1 digit max.
Other thermocouple inputs:
( 1% of PV or 4 C, whichever is greater) 1 digit max.
* 10 C for 100 C or less for K sensors
Platinum resistance thermometer inputs:
( 1% of PV or 2 C, whichever is greater) 1 digit max.
Analog inputs:
( 1% of FS) 1 digit max.
Models with thermocouple/platinum resistance thermometer
input (universal input):
Models with analog input:
Models with thermocouple/platinum resistance thermometer
input (universal input):
Models with analog input:
0 to 3999 s (in units of 1 s)
0 to 3999 s (in units of 1 s)
0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
250 ms
Thermocouple: 0.1 C/ max. (100
Platinum resistance thermometer: 0.4 C/ max. (10
20 M min. (at 500 VDC)
2,000 VAC, 50 or 60 Hz for 1 min (between terminals with
different charge)
10 to 55 Hz, 20 m/s
10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y,
and Z directions
100 m/s
300 m/s
Controller: Approx. 300 g, Mounting Bracket: Approx. 100 g
Controller: Approx. 250 g, Mounting Bracket: Approx. 100 g
Front panel: IP66 (indoor use),
Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
Emission Enclosure: EN55011 Group1 Class A
Emission AC Mains: EN55011 Group1 Class A
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
Immunity Surge: EN61000-4-5 1kV line to line
Immunity Voltage Dip/Interrupting:
UL 61010C-1
CSA C22.2 No.1010.1
EN61326, EN61010-1, IEC61010-1
VDE0106 Part 100 (Finger protection), when the terminal
cover is mounted.
1999 to 9999 (decimal point position depends on input type)
0.1 to 999.9 EU (in units of 0.1 EU) (See note 3.)
0.1 to 999.9 EU (in units of 0.1 EU) (See note 3.)
0.1 to 999.9% FS (in units of 0.1% FS)
0.01 to 99.99% FS (in units of 0.01% FS)
2
2
min., 3 times each in X, Y, and Z directions
min., 3 times each in X, Y, and Z directions
EN61000-4-2 4 kV contact discharge (level
2)
8 kV air discharge (level 3)
EN61000-4-3 10 V/m
(80-1000 MHz, 1.4-2.0 GHz amplitude
modulated) (level 3)
10 V/m (900 MHz pulse modulated)
EN61000-4-6 3 V
(0.15 to 80 MHz) (level 2)
EN61000-4-4 2 kV Power-line (level 3)
1 kV I/O signal-line (level 3) (See note 5.)
Power line, output line (relay output)
2 kV line to ground
Power line, output line (relay output)
1 kV line to ground
Input line (communication)
EN61000-4-11 0.5 cycle, 100% (rated
voltage)
2
for 10 min each in X, Y, and Z directions
max.) (See note 4.)
max.)
max.)
USB-Serial Conversion Cable
Note: A driver must be installed in the personal computer. Refer to
Communications Specifications
Note: The baud rate, data length, stop bits, and vertical parity can be
Current Transformer (Order Separately)
Ratings
Applicable OS
Applicable software
Applicable models
USB interface standard
DTE speed
Connector specifications
Power supply
Power supply voltage
Current consumption
Ambient operating temperature 0 to 55°C (with no condensation or icing)
Ambient operating humidity
Storage temperature
Storage humidity
Altitude
Weight
Transmission line con-
nection method
Communications
Synchronization
method
Baud rate
Transmission code
Data length (See note.) 7 or 8 bits
Stop bits (See note.)
Error detection
Flow control
Interface
Retry function
Communications
buffer
Send data wait time
Dielectric strength 1,000 VAC for 1 min
Vibration
resistance
Weight
Accessories
(E54-CT3 only)
installation information in the operation manual for the
Conversion Cable.
individually set using the Communications Setting Level.
5. When using the E53-AZB, E53-AZ01, or E53-AZ03 Option
Unit with the E5AZ-@3@M@@ to satisfy the immunity burst
requirements in the EN 61326 standard, always connect a
ZCAT2035-0930 Clamp Filter (manufactured by TDK) to the
cable for terminals 11, 12, and 13.
50 Hz, 98 m/s
E54-CT1: Approx. 11.5 g, E54-CT3: Approx.
50 g
Armatures (2)
Plugs (2)
RS-485 multipoint
RS-232C
RS-485 (two-wire, half duplex), RS-232C
Start-stop synchronization
1200, 2400, 4800, 9600, 19200, or 38400 bps
ASCII
1 or 2 bits
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with CompoWay/F or
CRC-16 Modbus
None
RS-485, RS-232C
None
40 bytes
0 to 99 ms
Default: 20 ms
Windows 2000/XP/Vista
Thermo Mini
E5CZ/E5CZ-U/E5AZ/E5EZ
Conforms to USB Specification 1.1.
38400 bps
Computer: USB (type A plug)
Temperature Controller: Setup Tool port
(on bottom of Controller)
Bus power (Supplied from USB host
controller.)
5 VDC
70 mA
10% to 80%
icing)
10% to 80%
2,000 m max.
Approx. 100 g
20 to 60°C (with no condensation or
2