PAXLTC00 Red Lion Controls, PAXLTC00 Datasheet - Page 7

METER THERMOCOUPLE 4-DIGIT

PAXLTC00

Manufacturer Part Number
PAXLTC00
Description
METER THERMOCOUPLE 4-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
Thermocoupler
Datasheet

Specifications of PAXLTC00

Display Style
Red Characters, Black Background
Display Type
LED Red
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
4
Display Digits - Height
0.560" (14.22mm)
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
85 V ~ 250 VAC
Applications
Thermocouple Input - Type T, E, J, K, R, S, B, N, or mV
Number Of Digits/alpha
4
No. Of Digits / Alpha
4
Meter Function
Temperature
Digit Height
14.2mm
Power Consumption
6VA
Operating Temperature Range
0°C To +50°C
Supply Voltage Ac, Min
85V
Signal Input Type
Selectable Thermocouple
Accuracy
0.8 °C, 2.1 °C, 2.3 °C °C
Brand/series
PAXL Series
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Display Resolution
1 °
Frequency
50⁄60 Hz
Function
Temperature
Number Of Digits
4
Primary Type
Electronic
Range, Measurement
-200 to +400 °C for T, -200 to +1000 °C for E, -200 to +760 °C for J, -200 to +1250 °C for K, 0 to +1768 °C for R, +150 to +1820 °C for B, -200 to +1300
Resolution
1 °
Standards
UL Recognized, CSA Certified, CE Approved
Temperature, Operating
0 to 50 °C
Temperature, Range, Measuring
-200 to +400 °C
Thermocouple Type
T
Voltage, Operating
85 to 250 VAC
Voltage, Supply
85 to 250 VAC
Character Size
0.56"
Display Font Color
Red
Rohs Compliant
NA
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
na, Contains lead / RoHS non-compliant
Other names
RLC116
which can be installed in the meter bezel display assembly. The unit of measure
for the meter display is then visible when the label backlight is illuminated. The
two most commonly used temperature unit labels (°F and °C) are supplied with
the meter. Press the up or down arrow keys to select whether the units label
backlight is illuminated. Press the PAR key to save the selection and advance
to the next parameter.
Mode, and press the PAR key. In Calibration Mode, the user can restore the
meter to factory default settings or recalibrate the signal input if necessary.
operation in Calibration Mode. Upon entering Calibration Mode, the meter
initially displays Code 50. Press the up or down arrow keys to select the access
code for the desired operation. If an access code other than those shown below
is entered, the meter exits Calibration Mode and returns to normal display mode.
previous section in the alternating display illustrations. All programming
parameters can be restored to the factory default settings by entering the access
Code 66 and pressing the PAR key. The meter briefly displays
returns to Code 50. This procedure resets only parameters that are accessed
through Programming Mode. The Calibration Mode settings (input calibration
levels) are not affected.
indicating incorrectly or inaccurately, refer to the troubleshooting section before
attempting this procedure. When re-calibration is required (generally every 2
years), the procedure should only be performed by qualified technicians using
appropriate equipment. A precision thermometer (RTD, thermistor or similar
type with an accuracy of ±0.3° C) and an accurate voltage source (0.01%) are
required. The procedure consists of setting the cold junction temperature and
applying accurate voltages to the meter input in a series of three steps. Allow a
60-minute warm-up before starting calibration.
5.0 C
The Units Label Kit Accessory contains a sheet of custom unit overlays,
To enter Calibration Mode, select
To prevent inadvertent entries, an access code must be entered to perform any
The factory settings for the programming parameters are shown in the
The meter has been fully calibrated at the factory. If the meter appears to be








ALIBRATING THE
METER INPUT CALIBRATION
UNITS LABEL BACKLIGHT
CALIBRATION MODE
FACTORY SETTINGS


to


< >

at the end of Programming

and then
M
ETER
7
COLD JUNCTION TEMPERATURE CALIBRATION
1. Connect a calibrated thermocouple (types T, E, J, K or N only) to the panel
2. Connect the reference thermometer to the measuring end of the thermocouple.
3. From the normal indicator display mode, compare the display temperature to
4. If cold junction re-calibration is necessary (temperature out of tolerance), enter
WHERE:
5. Press PAR. The meter briefly displays
VOLTAGE CALIBRATION
Enter  if input voltage calibration is desired. If  is entered, the meter exits
calibration and returns to normal display mode.
Calibration is now complete.
thermocouple type (
points over the range of the meter (-10 to +80 mV).
Calibration Mode. To exit Programming Mode without entering Calibration
Mode, select
returns to the normal display mode. All programmed selections are now
transferred to non-volatile memory and are retained if power is removed from
the meter.
and reprogram, if necessary, when power is restored.)
meter. Select the thermocouple type used in programming.
The two probes should be shielded from air movement and allowed sufficient
time to equalize in temperature. (As an alternative, the PAXLTC thermocouple
probe may be placed in a calibration bath of known temperature.)
that of the reference thermometer. Allow 10 minutes for the temperature to
equalize. The meter and the reference thermometer should agree to within 1° F
(0.6° C).
meter calibration mode and enter access Code 48. The meter display will
alternate between
the new cold junction temperature according to the formula:
New Cold Junction Reading = Old Cold Junction Reading + Difference
(Difference = Reference Thermometer Temperature - Meter Display Temperature)
junction value.
Following cold junction calibration, the display
The meter briefly displays
It is recommended to check calibration by selecting mV indication mode for
Before exiting Programming Mode, the meter offers the choice of entering
(If power loss occurs during Programming Mode, verify parameter changes
DISPLAY
  
  
  



PARAMETERS
30.000 mV
60.000 mV
0.000 mV
and press the PAR key. The meter briefly displays
PROGRAMMING MODE EXIT

 < > 
and the old cold junction reading. At this point, key-in

DESCRIPTION/COMMENT
Apply 0.000 mV, wait 20 seconds, press PAR.
Apply 30.000 mV, wait 20 seconds, press PAR.
Apply 60.000 mV, wait 20 seconds, press PAR.

and returns to the normal display mode.
) and verifying unit accuracy at various


to acknowledge the new cold

< >
/
appears.

and