PAXLTC00 Red Lion Controls, PAXLTC00 Datasheet - Page 3

METER THERMOCOUPLE 4-DIGIT

PAXLTC00

Manufacturer Part Number
PAXLTC00
Description
METER THERMOCOUPLE 4-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
Thermocoupler
Datasheet

Specifications of PAXLTC00

Display Style
Red Characters, Black Background
Display Type
LED Red
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
4
Display Digits - Height
0.560" (14.22mm)
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
85 V ~ 250 VAC
Applications
Thermocouple Input - Type T, E, J, K, R, S, B, N, or mV
Number Of Digits/alpha
4
No. Of Digits / Alpha
4
Meter Function
Temperature
Digit Height
14.2mm
Power Consumption
6VA
Operating Temperature Range
0°C To +50°C
Supply Voltage Ac, Min
85V
Signal Input Type
Selectable Thermocouple
Accuracy
0.8 °C, 2.1 °C, 2.3 °C °C
Brand/series
PAXL Series
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Display Resolution
1 °
Frequency
50⁄60 Hz
Function
Temperature
Number Of Digits
4
Primary Type
Electronic
Range, Measurement
-200 to +400 °C for T, -200 to +1000 °C for E, -200 to +760 °C for J, -200 to +1250 °C for K, 0 to +1768 °C for R, +150 to +1820 °C for B, -200 to +1300
Resolution
1 °
Standards
UL Recognized, CSA Certified, CE Approved
Temperature, Operating
0 to 50 °C
Temperature, Range, Measuring
-200 to +400 °C
Thermocouple Type
T
Voltage, Operating
85 to 250 VAC
Voltage, Supply
85 to 250 VAC
Character Size
0.56"
Display Font Color
Red
Rohs Compliant
NA
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
na, Contains lead / RoHS non-compliant
Other names
RLC116
UNITS LABEL KIT (PAXLBK)
the Units Label Kit. The backlight is controlled in the programming.
the meter’s bezel display assembly.
1. DISPLAY: 4-digit, 0.56" (14.2 mm) high red LED, minus sign displayed for
2. POWER: 85 to 250 VAC, 50/60 Hz, 6 VA
3. CONTROLS: Three front panel push buttons for meter set-up. Rear terminal
4. THERMOCOUPLE TYPES: T, E, J, K, R, S, B, N or mV scale
5. RESOLUTION: 1 degree for all types, or 0.1 degree for T, E, J, K and N only
6. THERMOCOUPLE RANGE AND ACCURACY: All errors include NBS
7. INPUT IMPEDANCE: 20 M, all types
8. LEAD RESISTANCE EFFECT: 20 μV/350 
9. OPEN THERMOCOUPLE DETECTION: Display Flashes: “
10. COLD JUNCTION COMPENSATION: Automatic, 0.02 degree/degree.
11. READING RATE: 2.5 readings/second
12. RESPONSE TIME: 2 seconds to settle for step input (increases with
13. LOW FREQUENCY NOISE REJECTION:
14. ENVIRONMENTAL CONDITIONS:
G
A
Each meter has a units indicator with backlighting that can be customized using
Each meter is shipped with °F and °C overlay labels which can be installed into
negative temperatures.
Overrange/Underrange Input: Flashing “
Overrange/Underrange Display: “       ” or “
Isolation: 2300 Vrms for 1 min. between input and supply (300 V working
input for disabling the front panel.
conformity, cold junction effect and A/D conversion errors at 23°C after 60
minutes warm-up. Relative Humidity less than 85%.
Max Input Voltage Protection: 70 VDC continuous
Disabled for linear mV scale.
programmable digital filtering)
Normal Mode Rejection: 45 dB @ 50/60 Hz (may be improved by
programmable digital filtering)
Common Mode Rejection: 120 dB, DC to 50/60 Hz
Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -40 to 80 °C
Operating and Storage Humidity: 85% max (non-condensing) from 0 to
50 °C
voltage)
TC TYPE
CCESSORIES
ENERAL
mV
E
K
R
S
B
N
T
J
-10.00 to +80.00 mV
+150 to +1820ºC
+302 to +3308ºF
-200 to +1000ºC
-200 to +1250ºC
-200 to +1300ºC
-328 to +1832ºF
-328 to +1400ºF
-328 to +2282ºF
-328 to +2372ºF
+32 to +3214ºF
+32 to +3214ºF
-200 to +400ºC
-200 to +760ºC
-328 to +752ºF
0 to +1768ºC
0 to +1768ºC
RANGE
M
ETER
ACCURACY

0.01%
      
0.8ºC
0.8ºC
0.8ºC
0.8ºC
2.1ºC
2.1ºC
2.3ºC
0.8ºC
1.4ºF
1.4ºF
1.4ºF
1.4ºF
3.8ºF
3.8ºF
4.1ºF
1.4ºF
” or “
S

PECIFICATIONS
WIRE COLOR
orange
purple
yellow

white
black
black
grey
blue
3
15. CERTIFICATIONS AND COMPLIANCES:
Note:
16. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use. One
17. CONNECTIONS: High compression cage-clamp terminal block
18. WEIGHT: 0.65 lbs. (0.24 Kg)
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
Shock According to IEC 68-2-27: Operational 30 g, 11 msec in 3 directions.
Span Drift: 40 ppm/°C
Zero Drift: 1 μV/°C
Altitude: Up to 2000 meters.
SAFETY
UL Recognized Component, File # E179259, UL61010-1, CSA C22.2 No. 61010-1
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
IECEE CB Scheme Test Report # 04ME11209-20041018
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
piece bezel/case. Flame resistant. Panel gasket and mounting clip included.
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
Immunity:
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
Surge
RF conducted interference
Voltage dip/interruptions
Emissions:
Emissions
direction for 1.5 hours, 2g’s.
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
Control and Laboratory use.
1. Criterion A: Normal operation within specified limits.
Issued by Underwriters Laboratories, Inc.
for measurement, control, and laboratory use, Part 1.
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 55011
Criterion A
4 kV contact discharge
8 kV air discharge
Criterion A
10 V/m
Criterion A
2 kV power
2 kV signal
Criterion A
1 kV L-L,
1 kV signal
Criterion A
3 V/rms
Criterion A
0.5 cycle
Class B
2 kV L&N-E power