K3HB-SSD 24VACVDC Omron, K3HB-SSD 24VACVDC Datasheet - Page 21

SENS LINEAR METER DC PROCES INPT

K3HB-SSD 24VACVDC

Manufacturer Part Number
K3HB-SSD 24VACVDC
Description
SENS LINEAR METER DC PROCES INPT
Manufacturer
Omron
Series
K3HBr
Type
Linear Sensor Meterr
Datasheets

Specifications of K3HB-SSD 24VACVDC

Measuring Range
0 ~ 20mA, 0 ~ 10V
Display Style
Green, Red Characters, Black Background
Display Type
LCD
Display Face Size
3.78" L x 1.89" W (96.0 x 48.0mm)
Display Digits
5
Display Digits - Height
0.193" (4.90mm), 0.559" (14.20mm)
Backlight
Green, Red
Mounting Type
Panel Mount
Termination
Screw Terminals
Voltage - Supply
24VAC/DC
Power Consumption
7W
Svhc
No SVHC (15-Dec-2010)
External Depth
95mm
External Length / Height
48mm
Ip/nema Rating
IP20
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Supply Voltage
RoHS Compliant
Approval Bodies
CE, CRUus, UL
Current Consumption
50mA
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
High-speed, High-precision
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
K3HB-SSD24VACVDC
K3HBSSD24VACVDC
Note: 1. DC power supply models require a control power supply capacity of approximately 1 A per Unit when power is turned ON. Particular
B-28
Output ratings (de-
pends on the model)
Display method
Main functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Accessories
2. PNP input types are also available
3. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for
attention is required when using two or more DC power supply models. The OMRON S8VS-series DC Power Supply Unit is recommend-
ed.
Thin Cables.
Linear Sensor Indicator
Relay output
Transistor output
Linear output
250 VAC, 30 VDC, 5 A (resistive load)
Mechanical life expectancy: 5,000,000 operations, Electrical life expectancy: 100,000 operations
Maximum load voltage: 24 VDC, Maximum load current: 50 mA, Leakage current: 100 µA max.
Linear output 0 to 20 mA DC, 4 to 20 mA:
Linear output 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC:
Negative LCD (backlit LED) display
7-segment digital display (Character height: PV: 14.2 mm (green/red); SV: 4.9 mm (green)
Scaling function, 2-input calculation function, measurement operation selection, averaging, previous average value
comparison, forced-zero, zero-limit, output hysteresis, output OFF delay, output test, teaching, display value selection,
display color selection, key protection, bank selection, display refresh period, maximum/minimum hold, reset
−10 to 55°C (with no icing or condensation)
25% to 85%
−25 to 65°C (with no icing or condensation)
2,000 m max.
Watertight packing, 2 fixtures, terminal cover, unit stickers, instruction manual. DeviceNet models also include a De-
viceNet connector (Hirose HR31-5.08P-5SC(01)) and crimp terminals (Hirose HR31-SC-121) (See note 3.)
K3HB-S
Load: 500 Ω max, Resolution: Approx. 10,000, Output error: ±0.5% FS
Load: 5 kΩ max, Resolution: Approx. 10,000, Output error: ±0.5% FS
(1 V or less: ±0.15 V; not output for 0 V or less)